Menu
Global B2B sourcing platform
Verified suppliers and manufacturers

100A 11kv 33kv Split Core CT Current Transformer

Price $45.00
Min Order 3 Pieces
Availability In Stock
Shipping From Beijing, China
Popularity 293 people viewed
Model NO.:
LZCK322-10
Application:
Electronic, Instrument
Type:
Current Transformer
Phase:
Single
Operation Condition:
Indoor
Usage:
Protection, Measurement
Winding Form:
Single Layer & Tightly Wound Type
Insulating Medium:
Common Insulating Materials
Installation:
Active Type
Magnetic Circuit Structure:
Single Stage Type
Voltage Transformation Principle:
Electromagnetic Type
Keyword:
100A Split Core Current Transformer
Model:
11kv 33kv Split Core CT
Standards:
IEC60044-1; IEC 61869-2; ANSI C57.13; Ntc 2205; G
Rated Primary Current:
30-600A
Rated Load:
10va
Rated Secondary Current:
5A or 1A
Weight (Kg):
1.6
Rated Frequency:
50Hz or 60Hz
Rated Short-Time Thermal Current:
40ka, 1s
Secondary Winding Power-Frequency Voltag:
3kv, 1min
Trademark:
GFUVE
Transport Package:
Standard Export Wooden Box
Specification:
50x110x52
Origin:
Beijing, China
Product Description
100A 11KV 33KV Split Core Ct Current Transformer

LZCK series split core current transformer is suitable forcurrent measurement and microcomputer protection of electrical equipment in 10KV and 35KV AC power system.It is widely used in compact fully insulated ring network switchgears such as ABB-Safe Ring/Safe Plus...and cable distribution boxes.The transformer can be directly installed at the inlet andoutlet cables.The slice is imported silicon material. Thesemicircular ring core and secondary windings arevacuum poured by insulated resin.
Parameters
Technical parameters
StandardsIEC60044-1; IEC 61869-2; ANSI C57.13; NTC 2205; GB1208-2006
Rated primary current30-600A
Rated load≤10VA
Rated frequency50Hz or 60Hz
Rated secondary current5A or 1A
Rated short-time thermal current40kA, 1S
Rated continuous thermal current120%I1n
Secondary winding power-frequency voltage3kV, 1min
Instrument security factorFS≤10
Mechanical parameters
Dimensions (W×D×H) (mm)φ50xφ110x52
Weight (kg)1.6
Operating conditions
Operating temperature-35°C to +55°C
Daily average temp<+40°C
Altitude<3500 meters
ConditionNo existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.
Technical data
TypeLZCK322-10LZCK322-10
PurposeMeasuring current transformerProtection current transformer
RatioAccuracy class and rated load(VA)Accuracy class and rated load(VA)
I1/I20.51310P1510P1010P5
30/1 11.5   
50/1 12  1.25
75/1 1.52.5 12
100/122.53 1.52.5
200/12.5  1.252.5 
300/13.75  1.252.5 
400/17.5  1.252.5 
500/110  1.253 
600/110  1.53 
50/5  2.5   
75/5  2.5   
100/52.5     
200/53.75     
300/55     
400/57.5   2.5 
500/57.5   2.5 
600/510   3.75 
Selection guide
 ModelPrimary rated currentRated loadAperture (mm)Description (mm)Weight (kg)MaterialWater-proof
LZCK-55100-1500A≤10VAφ55180×138×522PC IP65
LMCK185-10300-3000A≤25VAφ185350×283×554.5PC IP65
LZCK310-10300-600A≤10VAφ50φ50 x φ110 x 321Resinsilicon case (option)
LZCK322-1030-600A≤10VAφ50φ50 x φ110 x 521.6Resinsilicon case (option)
LZCK350-1020-600A≤25VAφ50φ50 x φ110 x 1053.1Resinsilicon case (option)
LZCG530-1030-600A≤20VAφ45φ45 x φ120 x 652.1Resinsilicon case (option)