$2.80
1000 Meters (MOQ)
All Aluminium Alloy Conductor AAAC for Electric Overhead Cable
HENAN BAOFENG CABLE CO., LTD.
Swipe or use the arrows to view product images.
11kv 12kv 15kv 24kv 25kv 33kv 35kv 36kv 40.5kv 42kv Medium Voltage Pre-Molded / Slip on Outdoor Termination for up to 42kv
| Price | $0.01 |
|---|---|
| Min Order | 1 Piece |
| Availability | In Stock |
| Shipping From | Guangdong, China |
| Popularity | 380 people viewed |
Model NO.:
HN15, HN20, HN30
Type:
Insulated
Conductor Type:
Solid
Application:
Underground, Transformer
Conductor Material:
Copper, Aluminum
Sheath Material:
Silicon Rubber
Insulation Material:
Silicon Rubber
Certification:
ISO9001, RoHS, VDE, Kema, Enel
Brand:
GCA
Cross-Section Range:
35-630mm2
Cable Shield Style:
Copper Wire, Copper Tape
Number of Cores:
1, 3
Rated Voltage:
15kV, 20kV, 35kV
Trademark:
GCA / United Electric
Transport Package:
Carton Box
Origin:
China
HS Code:
8546900000
Product Description
Medium Voltage Pre-molded Outdoor Termination for up to 42kV for XLPE Cable
• One-piece design with integrated stress cone.
• Quick and easy push-on installation.
• Long time storage, quick delivery.
• Waterproof lug special for outdoor termination.
• High quality silicone rubber, reliable insulation.
• Wide usage.
• Suitable for XLPE cable up to 42kV.
Features
• Power Cable Termination Voltage Class(kV): ≤ 42
• Cable Shield Style: Copper wire, copper tape
• Number of Cores: 1, 3
• Application Type: Outdoor
• Industry Standards: Design Specification GB/T 12706.4, IEC 60502-4
1.cable lug
2.pre-molded outdoor termination
3.semi-conductive tape
4.copper tape screen
5.heat shrinkable protective tube
6.heat shrinkable breakout
7.copper braid
15kV outdoor termination
2.pre-molded outdoor termination
3.semi-conductive tape
4.copper tape screen
5.heat shrinkable protective tube
6.heat shrinkable breakout
7.copper braid
15kV outdoor termination
Specification
| RXS/GCA HW15 | RXS/GCA HW20 | RXS/GCA HW35 | |||
| Conductor size (mm2) | Core insulation outer dia. min/ max(mm) | Conductor size (mm2) | Core insulation outer dia. min/ max(mm) | Conductor size (mm2) | Core insulation outer dia. min/ max(mm) |
| 25 | 15.0-41.0 | 35-50 | 19.0-41.0 | 50-70 | 30.0-61.0 |
| 35-50 | 70-95 | 95-120 | |||
| 70-95 | 120-150 | 150-185 | |||
| 120-150 | 185 | 240 | |||
| 185-240 | 240 | 300 | |||
| 300 | 300 | 400 | |||
| 400 | 400 | 500 | |||
| 500 | 500 | 630 | |||
| 630 | |||||
Technical Data
| Test item | 8.7/15(17.5)kV | 12/20(24)kV | 26/35(42)kV |
| A.C. voltage withstand test | No flashover, no breakdown at 39kV for 5min. | No flashover, no breakdown at 54kV for 5min. | No flashover, no breakdown at 117kV for 5min. |
| Partial discharge test | 15kV, <2pC | 20kV, <2pC | 45kV, <2pC |
| Heating cycles voltage test | 63 cycles at 95-100°C, 23kV | 63 cycles at 95-100°C, 30kV | 63 cycles at 95-100°C, 65kV |
| Impulse voltage withstand test at 95- 100°C | No flashover, no breakdown at 10 positive and 10 negative impulses at 95kV | No flashover, no breakdown at 10 positive and 10 negative impulses at 125kV | No flashover, no breakdown at 10 positive and 10 negative impulses at 200kV |
| Thermal short-circuit test | No deformation or welding at 31.0kA,2.02s and 31.1kA,2.02s | No deformation or welding at 31.0kA,2.03s and 31.0kA,2.02s | No deformation or welding at 31.0kA,2.03s and 30.8kA,2.04s |
| Dynamic short-circuit test | No deformation or welding at 112.3kA,60ms | No deformation or welding at 111.3kA,60ms | No deformation or welding at 112.2kA,60ms |
| 15min, A.C. voltage withstanding test | 23kV, 15min. no flashover, no breakdown | 30kV, 15min. no flashover, no breakdown | 65kV, 15min.no flashover, no breakdown |
Application
15kV outdoor termination used in Guangzhou 20kV outdoor termination used in Iran
- Similar Products
$0.50
20000 Meters (MOQ)
CCA Conductor Spt Cable 2*12AWG Cable Wire
Zhengzhou Jinshui Industry and Commerce Co., Ltd.