Menu
Global B2B sourcing platform
Verified suppliers and manufacturers

12kv High Voltage Outdoor Sf6 Electric Pole Mounted Auto Recloser Load Break Switch Vacuum Circuit Breaker

Price $1800.00
Min Order 1 Piece
Availability In Stock
Shipping From Zhejiang, China
Popularity 398 people viewed
Model NO.:
ZW32-12
Breaking Capacity:
High Voltage Circuit Breakers
Operation:
Manual Type
Arc-extinguishing Medium:
Vacuum
Installation:
Fixed
Type:
Circuit Breaker
Function:
Conventional Circuit Breaker, Overcurrent Protection
Certification:
ISO9001-2000
Rated Frequency:
50Hz
Rated Voltage:
12kv
Rated Current:
630/1250A
Rated Short-Circuit Breaking Current:
20/25ka
Trademark:
DGG
Transport Package:
Export Box
Origin:
China
HS Code:
8504311000
Product Description
Our factory

We are professional manufacturer of current transformer ,voltage transformer, Vacuum Circuit Breakers/Recloser,Isolation switches,Dropout Fuse Cut-out,Lightning Arresters,High and Low Voltage Cabinets,Metering Devices,Power Distribution Transformers  etc.


General

ZW32-12 Series outdoor AC vacuum circuit breaker is 12kV distribution equipment of 3 phase,50Hz. It's used to connect and break load current,over-load current, and short-circuit current. It's applicable for substations, industry, mining, and urban and rural electric power networks, especially applicable on occasions with frequent operation and automatic power distribution networks.

Model and Meanings

Technical specification
No.ItemUnitData
1Rated frequencyHz50
2Rated voltagekV12
3Rated currentA630/1250
4Rated short-time power frequency withstand voltageInterphase, to earth(wet)kV/min42/1
Interphase, to earth(dry)48/1
Break(dry)34/1
Secondary circuit to earth2/1
5Rated lightning impulse withstand voltageInterphase, to earthkV75
Break85
6Rated short-circuit breaking currentkA20/25
7Rated short-circuit making current(peak) 50/63
8Rated short-time withstand current and durationkA/s(20/25)/4
9Rated peak withstand currentkA50/63
10Rated short-circuit breaking current breaking timesTimes30
11Rated operating voltage and rated voltage of the auxiliary circuitVAC/DC220,DC48,DC24
12Main circuit resistanceWithout isolationμΩ≤80
With isolation ≤120
13Mechanical lifeTimes10000
Note: If the altitude is over 1000m, the rated insulation level should be modified as appropriate.
 