Swipe or use the arrows to view product images.
20ka 1p+Npe Type 2+3 Surge Protective Devices (SPD) Class 2
| Price | $5.00 |
|---|---|
| Min Order | 50 Pieces |
| Availability | In Stock |
| Shipping From | Zhejiang, China |
| Popularity | 257 people viewed |
Model NO.:
LY1-D20 1P+NPE 275V
Gw:
19.4kgs
in:
10ka(8/20us)
Uoc:
20kv
up:
1.3ka
OEM Service:
Yes
Delivery Way:
FedEx, DHL, UPS, Aramex,EMS
Lead Time:
3-5 Days
Trademark:
LEEYEE
Transport Package:
80PCS/CTN
Specification:
41x22x31cm
Origin:
China
HS Code:
8536300000
Product Description
Product Description
Application
This T2 spd surge protective device is applied low voltage standard IEC EN 61643-11 to protect against AC power line system and other equipment from over voltage and instantaneous over voltage damage. Widely used in photovoltaic comber box, power inverter, DC distribution cabinet etc. It has advantages of large discharge current, fast respond time, low residual voltage.The max. PV voltage up to Uc ≤275V .Features
1. Prewired complete unit consisting of a base part and plug-in protection modules
2. High discharge capacity due to heavy duty zinc oxide varistors
3. High reliability due to 'temperature-controlled' SPD monitoring device
2. High discharge capacity due to heavy duty zinc oxide varistors
3. High reliability due to 'temperature-controlled' SPD monitoring device
4 .Din rail installation, easy to install.
5. Inside over-current, over-heat, temperature control open circuit.
6. Fast response time, low residual voltage.
7. Window color indicates working condition, green means normal, red means fault.
5. Inside over-current, over-heat, temperature control open circuit.
6. Fast response time, low residual voltage.
7. Window color indicates working condition, green means normal, red means fault.
8. Class II T2 protection degree.
Installation position
The cross-sectional area of ground wire should not be less than 4 mm2, and the length of total lead not more than 0.5m.
0.5MM
The minimum distance from any earthed conductive surface at which the SPD can be installed is 8mm.
Connection of remote signalling alarm: the SPD is provided with remote signalling interfaces (NC, COM and NO, normally closed), applicable for remote centralized monitoring or alarm. After the connection, check if the module is fitted in. If so, NC and COM are closed; if not, repress the module.
| IEC Electrical | 75 | 150 | 275 | 320 | 385 | 440 | |
| Nominal AC Voltage (50/60Hz) | Uo/ Un | 60 V | 120 V | 230 V | 230 V | 230 V | 400 V |
| Maximum Continuous Operating Voltage (AC) | Uc | 75 V | 150 V | 275V | 320 V | 385 V | 440 V |
| Nominal Discharge Current (8/20 μs) | In | 10 kA | 10 kA | 10 kA | 10 kA | 10 kA | 10 kA |
| Maximum Discharge Current (8/20 μs) | Imax | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA |
| Voltage Protection Level | Up | 0.2 kV | 0.6 kV | 1.3 kV | 1.5 kV | 1.5 kV | 1.8 kV |
| Response Time | tA | < 25 ns | |||||
| Back-Up Fuse (max) | 125 A gL / gG | ||||||
| Short-Circuit Current Rating (AC) | ISCCR | 10 kA | |||||
| TOV Withstand 5s | UT | 90V | 180V | 335V | 335V | 335V | 580V |
| TOV 120min | UT | 115V | 230V | 440V | 440V | 440V | 765V |
| mode | Withstand | Withstand | Safe Fail | Safe Fail | Safe Fail | Safe Fail | |
| Mechanical & Environmental | |||||||
| Operating Temperature Range | Ta | -40ºF to +158ºF [-40ºC to +70ºC] | |||||
| Permissible Operating Humidity | RH | 5%...95% | |||||
| Atmospheric pressure and altitude | 80k Pa ... 106k Pa / -500 m.....2000 m | ||||||
| Terminal Screw Torque | Mmax | 39.9 Ibf ·in [4.5 Nm] | |||||
| Conductor Cross Section (max) | 2 AWG (Solid, Stranded) / 4 AWG (Flexible) | ||||||
| 35 mm2 (Solid, Stranded) / 25 mm2(Flexible) | |||||||
| Mounting | 35 mm DIN Rail, EN 60715 | ||||||
| Degree of Protection | IP 20 (built-in) | ||||||
| Housing Material | Thermoplastic: Extinguishing Degree UL 94 V-0 | ||||||
| Thermal Protection | Yes | ||||||
| Operating State / Fault Indication | Green ok / Red defect | ||||||
| Remote Contacts (RC)RC Switching CapacityRC Conductor Cross Section (max) | OptionalAC: 250V / 0.5 A; DC: 250V / 0.1 A;125V / 0.2 A;75V / 0.5 A16 AWG (Solid) / 1.5 mm2(Solid) | ||||||
Internal Configuration
2P
1P+NPE
Dimensions & Packaging
2P
1P+NPE
Connection Diagram
2P
1P+NPE
- Similar Products
Negotiable
1000 Pieces (MOQ)
5.5*6mm Gas Discharge Tube Full Range of Voltage Gdt
Ningbo Zhengmao Electronics Co., Ltd.
$7.00
2000 Pieces (MOQ)
Bxst V006-100-3 DIN Rail Over and Under Wiring Voltage Protector
Wenzhou BXST Co., Ltd.
$3.74
2000 Pieces (MOQ)
Bx-V518-DV 40A Single Phase Adjustable Over and Under Voltage Protector
Wenzhou BXST Co., Ltd.