Swipe or use the arrows to view product images.
350kw Dry Type Three Phase Isolation Transformer (1 loop) with Cabinet
| Price | $25000.00 |
|---|---|
| Min Order | 1 Piece |
| Availability | In Stock |
| Shipping From | Guangdong, China |
| Popularity | 237 people viewed |
Model NO.:
BC-E00033A
Application:
Power, Electronic, Instrument, Rectifier
Phase:
Three
Core:
Core-type Transformer
Cooling Method:
Dry-type Transformer
Winding Type:
Multi-winding Transformer
Certification:
ISO9001, CCC
Usage:
Rectifier Transformer, Combined Transformer, Power Transformer
Frequency Characteristics:
Power Frequency
Shape of Core:
Silicon Steel Sheet
Brand:
Bc Power
Supply Voltage Fluctuation:
<+/-5%
Temperature Sampling:
Ntc Resistor Temperature Switch
Isolation Grade:
Class H (180 C)
Rated Capacity:
350kw
Working Frequency:
50Hz~70Hz
Impedance Voltage:
<6%
Efficiency:
>97.5%
Noise:
<70dB
Allowable Temperature Rise:
<95K
Transport Package:
Wooden Case
Specification:
1500*1200*1800 mm, 220V/400V/480V/540V/600V/800V
Origin:
Dongguan City, Guangdong Province, China
Product Description
1. The primary side is 1 loop with 6 contactors are configured each to control the output of 220V/400V/480V/540V/600V/800V separately.
2. Push-button switch is used to control the output of the contactor. The loop contactor interlock can only have one voltage output.
3. The equipment is equipped with temperature monitoring (winding temperature, core temperature) switching, and the fan is started to cool when the internal temperature is higher than 60 degrees Celsius, and the fan is stopped when the internal temperature is lower than 45 degrees Celsius. Alarm sound occurs when the internal winding temperature exceeds135 degrees Celsius. The transformers automatically shuts down the total input power when the temperature is greater than 150 degrees Celsius.
4. Product total weight nearly 2000KG.
Electric Characteristics
2. Push-button switch is used to control the output of the contactor. The loop contactor interlock can only have one voltage output.
3. The equipment is equipped with temperature monitoring (winding temperature, core temperature) switching, and the fan is started to cool when the internal temperature is higher than 60 degrees Celsius, and the fan is stopped when the internal temperature is lower than 45 degrees Celsius. Alarm sound occurs when the internal winding temperature exceeds135 degrees Celsius. The transformers automatically shuts down the total input power when the temperature is greater than 150 degrees Celsius.
4. Product total weight nearly 2000KG.
Electric Characteristics
| 1 | Connection Group | Dyn11 |
| 2 | Rated capacity of primary winding | 350kW |
| 3 | Rated capacity of sencondary winding | 350kW |
| 4 | Primary rated line voltage (N1) | (220/400/480/540/600/800) *1 / Y connection, with N At 400V and above to meet the full power, The total power at 220V is 193KW |
| 5 | Secondary rated line voltage (N2) | 380V / D connection |
| 6 | Primary side impedence | / |
| 7 | Mains voltage fluctuation | < +/-5% |
| 8 | Working frequency | 50~70Hz |
| 9 | Efficiency | >97.5% (350kW resistive load) |
| 10 | The load cycle | Continous operation |
| 11 | Impedance voltage | <6% |
| 12 | Type of transformer | Dry type |
| 13 | The temperature sampling | Thermistor (NTC) temperature switch |
| 14 | Isolation resistance | P,S,E>500MΩ DC2500V/60s |
| 15 | Dielectric strength | <20mA 3KVAC/60s Coil-Core N1-N2 |
| 16 | Isolation grade | H(180ºC) |
| 17 | Allowable temperature rise | 95K (rated current, forced air cooling) |
| 18 | Noise | <70dB (measured with a sound level meter at 1m) |
| 19 | Cooling type | AF (Forced air cooling, control panel with independent control switch) |
- Similar Products
Negotiable
2 Pieces (MOQ)
Type Outdoor High Voltage Box Substation Prefabricated Cabin
Donghe Electric Trading (Yueqing) Co., Ltd.