$200.00
5000 Meters (MOQ)
Copper Conductor Flexible Cable Rvv 5core6.0mm2 Electrical Wire Power Cable
Haiyan Hetai Cable Co., Ltd
Swipe or use the arrows to view product images.
6kV 10kV 11kV 15kV 20kV 25kV 30kV 33kV 35kV Heat shrinkable power cable indoor termination for 1 core XLPE 120~185sq.mm
| Price | $1.20 |
|---|---|
| Min Order | 10 Sets |
| Availability | In Stock |
| Shipping From | Guangdong, China |
| Popularity | 430 people viewed |
Model NO.:
UE-HTIX-120-185-1
Type:
Insulated
Conductor Type:
Stranded
Application:
Underground, Transformer
Conductor Material:
Copper
Sheath Material:
Polyolefin
Insulation Material:
Polyolefin
Certification:
ISO9001, RoHS
Brand:
United Electric
Trademark:
United Electric
Transport Package:
Carton Box
Specification:
25-630sq. mm
Origin:
China
HS Code:
8546900000
Product Description
Medium Voltage Heat Shrinkable Termination up to 36kV
Features
1. Suitable for 1-core, 3-core polymeric and paper insulated cable with or without armour. Rated voltage comply with IEC 60183 and CELENEC HD 629.1 S2, HD 629.2 S2. Such as 3.6/6(7.2)kV, 3.8/6.6(7.2)kV, 6/10(12)kV, 6.35/11(12)kV, 8.7/15(17.5)kV, 12/20(24)kV, 12.7/22(24)kV, 18/30(36)kV, 19/33(36)kV.
2. Consists of indoor & outdoor termination for polymeric insulated and paper insulated cable.
3. Excellent electrical stress release property achieved by heat shrinkable stress control tubing at the screen cut.
4. High electrical insulation value and unrestricted shelf life.
5. Water & moisture proof and good mechanical strength.
6. Good resistance against UV-radiation and chemicals.
7. Outstanding environmental resistance and good performance in polluted area.
8. The products are fully in accordance with IEC 60502-4, CELENEC HD 629.1 S2, HD 629.2 S2 and other standards such as BS, DIN and VDE
Selection guige
Technical specification for medium voltage indoor termination
| Test Item | Voltage Um (kV) | Test result | ||||
| 7.2 | 12 | 17.5 | 24 | 36 | ||
| A.C. voltage dry withstand, 5min | 17 | 27 | 39 | 54 | 81 | No breakdown or flashover |
| Partial discharge | 6 | 11 | 15 | 20 | 30 | <10pC |
| Impulse voltage | 60 | 75 | 95 | 125 | 170 | No breakdown or flashover |
| A.C. voltage dry withstand,15min | 9 | 15 | 23 | 30 | 45 | No breakdown or flashover |
| Humidity, 300h | 4.5 | 7.5 | 11 | 15 | 22.5 | No failure or flashover |
Technical specification for medium voltage outdoor termination
| Test Item | Voltage Um (kV) | Test result | ||||
| 7.2 | 12 | 17.5 | 24 | 36 | ||
| A.C. voltage dry withstand, 5min | 17 | 27 | 39 | 54 | 81 | No breakdown or flashover |
| Partial discharge | 6 | 11 | 15 | 20 | 30 | <10pC |
| Impulse voltage | 60 | 75 | 95 | 125 | 170 | No breakdown or flashover |
| A.C. voltage dry withstand,15min | 9 | 15 | 23 | 30 | 45 | No breakdown or flashover |
| Salt fog, 1000h | 4.5 | 7.5 | 11 | 15 | 22.5 | No failure or flashover |
Testing
Application
- Similar Products
$10.00
500 Pieces (MOQ)
Stranded Copper Clad Aluminum Wire, Stranded CCA Wire
ZHEJIANG MEITONG CONDUCTOR TECHNOLOGY CO., LTD.
$0.10
3000 Meters (MOQ)
18 AWG Flexible Silicone Wire High Temperature Wire for UL3239
Dongguan Dewei Wire Co., Ltd.