Menu
Global B2B sourcing platform
Verified suppliers and manufacturers

72.5kv-132kv-230kv Capacitor Voltage Transformer (CVT)

Price $100000.00
Min Order 10 Pieces
Availability In Stock
Shipping From Zhejiang, China
Popularity 501 people viewed
Model NO.:
CVT
Type:
High Frequency Ceramic Capacitor
Application:
Power
Packaging Type:
Through Hole
Structure:
Fixed Capacitor
Usage:
High Frequency Coupling
Trademark:
HEMG
Transport Package:
Wooden
Specification:
300KV
Origin:
China
Product Description




This series of capacitor voltage transformers include the products with the type of TYO 150/\/'3-0.01 H (TYD161/v3-0.01 H), TYD150~13-0.02H (TYD161/v3-0.02H), TYD220~-0.00SH, TYD220~- 0.01 H, TYD330kv/110v-0.00SH, TYD330kv/115v-0.01H, TYD500kv~110v-0.00SH etc., which can be used for electric measurement and relay protection in the electric power system with a voltage of 150~500kV and frequency of 50Hz. The products are in accordance with the requirements of the standard GB 4 703 "Capacitor Voltage Transformers",GB19749 "Coupling capacitors and capacitor voltage dividers" & IEC 60044-5 "Capacitor Voltage Transformers".

 
TECHNICAL DATA SCHEDULE
    CAPACITOR VOLTAGE TRANSFORMER 330 kV
CODE NO: 4132
ITEMDESCRIPTIONUNITSREQUIREDGUARANTEED
1.0Manufacturer   
1.1Type--Capacitive
1.2
1.3
Model no  
Country of Origin
-
-
-
 
TYD330/3-0.0044H
     
2.0Nominal characteristics   
2.1Voltage   
2.1.1Rated voltagekV330330
2.1.2Rated voltage classKV362362
2.2Rated frequencyHz5050
2.3Network neutral grounding-EffectiveEffective
2.4Rated voltage factor for 30 s-1,51.5
2.5Rated lightning impulse withstandkV11751175
2.6Chopped lighting impulse withstand (3 ms)kV12901290
2.7Switching impulse withstand (wet)kV950950
2.8Power frequency withstand voltage (1 min)kV450450
2.9Creepage distancemm/kV3131
2.10Max. radio interference voltage at 0,5 MHz per IEC 694mV25002500
2.11Capacitance C1 and C2pf44004400
2.12Series reactor
- inductance range
- resistance range
 
mH
ohms
 
0.2
-
0.2
 
400
2.13Transformation ratio-  330kV/Ö3
 : 0,11kV/Ö3
 : 0,11kV/Ö3
 (: 0,11kV/Ö3)
330kV/3
: 0,11kV/3
: 0,11kV/3
     
2.14Transformer characteristics
- HV/LV turn ratio range
- Normal operating flux density
 
-
tesla
 
-
-
 
3000:1
0.5T
2.15Primary voltagekV330/Ö3330/Ö3
2.16Secondary voltageV110/Ö3110/Ö3
2.17Winding accuracy:   
 - metering class-0,20,2
 - protection class-3P3P
 - burden ( on each winding)VA5050
2.18Number of secondary winding-2 (3)2
2.19Winding conductor-CuCU
2.20Circuit Diagram-To be enclosed with bidTo be enclosed with bid
2.21HV Terminal connector for-TBA 
     
3.0Weights and Dimensions   
3.1Weight for operationkg-950
3.2Weight for transportkg-1000
3.3Heightm-4370
3.4Shipping dimensions (H x W x D)m-800*700*2600
3.5Outline drawing number-To be enclosed with bidTo be enclosed with bid
4.0Type tests reports N°-To be enclosed with bidTo be enclosed with bid
5.0Standards-IEC 60044-5
IEC 60694
  IEC 60947-1
IEC 60044-5
IEC 60694
IEC 60947-1
6.0Quality control-ISO -----------ISO9001
     
7.0Installation-Outdoor, Substation SwitchyardOutdoor, Substation Switchyard
8.0Installation-Outdoor in substation switchyard 
  • Similar Products