Menu
Global B2B sourcing platform
Verified suppliers and manufacturers

CJB20-630 EN50181 11kV 12kV 15kV 24kV 25kV 630A Dead Break Screened Separable Tee Connector (Interface C) with Mechanical Lug (Front Tee)

Price $1.00
Min Order 1 Piece
Availability In Stock
Shipping From Guangdong, China
Popularity 410 people viewed
Model NO.:
CJB20-630
Interface/Bushing:
Type C (EN50181)
Rated Voltage:
10kV, 20kV
Rated Current:
630A
Cable Lug:
Mechanical Type
Material:
Silicone Rubber
Type Tested:
Yes
Cable Shield Style:
Copper Wire, Copper Tape
Armour:
Unarmored, Steel Tape, Steel Wire
Trademark:
GCA
Transport Package:
Carton Box
Origin:
China
HS Code:
8546900000
Product Description

CJB20-630 -24kV 630A  Dead Break Screened Separable Front Tee Connector (Interface C1)


Interface C1 bushing (630A)
CJB20-630 and CJBK20-630 are made of silicone rubber, suit for connecting with type C1 bushing as described by CENELEC EN 50180, 50181 and DIN 47636.
CJB20-630
The screened separable tee connector CJB20-630 is designed to connect the polymeric cable to transformers, switchgears and other equipment.
CJBK20-630

The screened separable connector CJBK20-630 is application for dual cable arrangement, designed to be used with CJB20-630 screened separable tee connectors.

 
Design 

 Type C1 bushing
• Stud + nut + washers
• Insulating back plug (with test point is available)
• Cable lug (compression and mechenical type are available)
• Inner screen layer
• Insulation layer
• Outer screen layer
• Stress cone
• arthing wire
• Cable core
• B type connecting rod


Selection guide
 
Kit reference
(No.)
Suit for diameter over XLPE insulation (mm) Suitable cable size (sq.mm)
Um=17.5kV Cable Um=24kV Cable
CJB20-1250-1#, CJBK20-1250-1# 16.5-23 35, 50, 70, 95 25, 35, 50, 70
CJB20-1250-2#, CJBK20-1250-2# 23-28 120, 150, 185 95, 120, 150
CJB20-1250-3#, CJBK20-1250-3# 28-36 240, 300, 400 185, 240, 300
CJB20-1250-4#, CJBK20-1250-4# 36-40 500 400, 500
CJB20-1250-5#, CJBK20-1250-5# 40-45 630630


Technical data
Test Item Test value
AC voltage withstand 54kV, 5min
AC voltage withstand 30kV, 15min
Partial discharge 20kV, ≤10pC
Heating cycles voltage test 30 cycles in air, 30 cycles under water at 95-100°C, 30kV
Thundering impulse voltage withstand 125kV at 10 positive and 10 negative
Screen resistance Not exceed 5000Ω
Screen leakage current Maximum 0.5mA at 24kV
Thermal short-circuit test No visible deterioration at 37.3kA, 2s
Dynamic short-circuit test No visible deterioration at 131.9kA, 10ms
Type test was performed in Guangdong Testing Institute of Product Quality Supervision (GQI), which is accredited in accordance with ISO/IEC
17025 General Requirements for the Competence of Testing and Calibration Laboratories. Type test reference standard: IEC60502-4:2005.