Model NO.:
DAM3-250
Breaking Capacity:
Low Voltage Circuit Breakers
Operation:
Manual Type
Speed:
Normal Type Circuit Breaker
Arc-extinguishing Medium:
Arc Chamber
Installation:
Fixed
Structure:
MCCB
Poles Number:
3
Type:
Circuit Breaker
Function:
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection
Certification:
ISO9001-2000, CE, CB, CCC, RoHS
Base:
BMC Unflaming Material
Terminal:
with Terminal Box
Trademark:
CDADA, OEM, ODM
Transport Package:
Carton
Specification:
63, 80, 100, 125, 160, 200, 250A
Origin:
Shanghai, China
HS Code:
8536200000
Product Description

Overview


The rated current of the Dada DAM3-250 molded case circuit breaker can reach up to 250A. These electrical devices are suitable for power distribution circuits with an alternating current of 50-60Hz and a rated operating current to 1000A. They can also be used in electric motors for infrequent starting and overload protection as well as protection against short circuiting and undervoltage conditions.

Compared to the DAM1 series, the DAM3 series are designed for smaller volume, higher breaking capacity, offering better energy savings.

Electrical parameters of DAM3-250 molded case circuit breaker
Rated current of frame size Inm [A] 250
Rated current [A]100-250100-225
Number of poles2 / 3 / 4
Rated operating voltage(AC)50-60HZ [V]400/690
DC [V]250/1000
Rated impulse withstand voltage Uimp [KV]8
Rated insulation voltage Ui [V]750
Test voltage at industrial frequency for 1 min [V]3000
Rated ultimate short-circuit breaking capacity Icu [KA]BCNS
(AC)50-60HZ 220/230V [KA]30365075
(AC)50-60HZ 400/415V [KA]18253650
(AC)50-60HZ 690V [KA]681215
(DC)250V-2 Poles in series18223040
(DC)500V-2 Poles in series9121520
(DC)750V-4 Poles in series16182230
(DC)1000V-4 Poles in series13151825
Rated service short-circuit breaking capacity, Ics [KA]    
(AC)50-60HZ 220/230V [%Icu]60%60%60%50%
(AC)50-60HZ 400/415V [%Icu]60%60%60%50%
(AC)50-60HZ 690V [%Icu]60%60%60%50%
category of utilization (EN 60947-2)A
Isolation conditionBitmap
Reference standardIEC/EN 60947-2/GB 14048.2
InterchangeabilityBitmap
VersionsFixedBitmap
Plug-inBitmap
Draw-out-

Physical parameters DAM3-250 molded case circuit breaker
EnduranceTotal cycles10000
Electrical endurance1500
Mechanical endurance8500



Basic dimensions-fixed version
3/4 Poies W[mm]70(2P) /104 /139
3/4 Poies H[mm]5962.5
H1[mm]78.582
3/4 Poies L[mm]139

Introduction
The DAM3-250 molded case circuit breaker automatically cuts off the current when the current exceeds the release setting. The molded case refers to the plastic insulator used as the frame of the device to insulate the conductor and the metal grounding component.

Working principle
The main contact of DAM3-250 molded case circuit breaker is manual manipulation or electric closing. After the main contact is closed, the free release mechanism locks the main contact into the closing position. The overcurrent trip coil and the thermal trip element are connected in series with the main circuit. The undervoltage trip coil and the power supply are connected in parallel.














  • Similar Products