Menu
Global B2B sourcing platform
Verified suppliers and manufacturers

Compact Automatic Vacuum Circuit Recloser with Built-in CT and Voltage Transducer

Price $1000.00
Min Order 1 Piece
Availability In Stock
Shipping From Zhejiang, China
Popularity 428 people viewed
Model NO.:
TOVR
Breaking Capacity:
High Voltage Circuit Breakers
Operation:
Manual Type
Speed:
Normal Type Circuit Breaker
Arc-extinguishing Medium:
Vacuum
Installation:
Fixed
Structure:
Vacuum Circuit Breaker
Poles Number:
3
Type:
Circuit Breaker
Function:
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection)
Certification:
ISO9001-2000, CE
Standard:
IEC 60056,62271
Rated Voltage:
36kv
Rated Current:
630A, 800A
Mechanical Life:
10000
Electrical Life:
E2
Operating Mechanism:
Permanent Magnet
Weight:
25kg
Altitude:
2000m
Protection:
IP65
Delivery Time:
Within 30 Days
Trademark:
TENLEE
Transport Package:
Wooden Box
Specification:
embedded pole, mechanism, built-in CT&VT
Origin:
China
HS Code:
8535210000
Product Description
Product Description

TOVR outdoor high-voltage AC vacuum circuit breaker automatic recloser (hereinafter referred to as "recloser") adopts the vacuum arc extinguishing principle. It is a three-phase AC 50Hz/60Hz outdoor high voltage switch. It is mainly applied in rural and urban power grids, 10-35kV outdoor power distribution system to divide and combine load current, overload current and short-circuit current; it can also be used in other similar places. The TOVR series outdoor AC high-voltage vacuum circuit breaker auto recloser complies with standards GB 1984 "AC High-Voltage Circuit Breaker" and the International Electrotechnical Commission IEC 60056 "High-Voltage AC Circuit Breaker".

Standard
IEC62271-100/105/200, IEC60265-200,


Service condition:
-Ambient air temperature: -40 °C ~ 60 °C
- Altitude: no more than 2000m
- The surrounding air may be contaminated by dust, smoke, corrosive gases, steam or salt spray;
- The wind speed does not exceed 34m/s (equivalent to 700Pa on the cylinder surface);
- Vibration or ground motion from switchgear and control equipment can be ignored;
- Pollution level: Level III.
- If service in a different condition, please negotiate with the manufacturer.

 

Product Parameters
No.Item Unit Data 
1Rated voltagekV34.5
2Maximum operating voltage (nominal)kV36.2
3Rated current630/800
4Rated frequency Hz 50/60
5Rated short circuit making current kA12.5/16
6Rated short circuit breaking currentkA12.5/16
7Rated short time withstand currentkA12(16)/3s
8Rated peak withstand currentkA32.5/42
9Rated operating sequence o-0.3s-co-180s-co
10Rated power frequency withstand voltage (dry/wet)kV70/1min
11Auxiliary and control circuitkV2/1min
12Rated lightning impulse withstand voltage kV150
13Rated short circuit current breaking times E2
14Mechanical life 10000
15Main circuit resistanceμΩ≤200
 
Detailed Photos
installation





 
Packaging & Shipping
standard packaging: 
wooden box
delivery time: 
within 20 days


shipping:
sea, air, railway, express

Company Profile

Combining manufacturing experience, new technology and industrial knowledge, TENLEE aims to build advanced power distribution and protection systems. 
TENLEE is specialized in manufacturing a comprehensive range of solutions from 12kv to 40.5kv for indoor/outdoor systems: gas insulated switchgears 
ring main unit
sf6 free switchgears
vacuum circuit breakers
sf6 circuit breakers
reclosers 
load break switches
disconnectors
distribution transformers/power transformers
substations 

FAQ

1. What is the delivery date?
Usually within a month for a HQ.
2. Do you have type tests?
Yes, we have type test in China and we also pass type test in Europe. 
3. Do you have other voltage ranges?
Yes, we have 12kv, 24kv and 40.5kv. 

  • Similar Products
Full Page Contact Supplier