Menu
Global B2B sourcing platform
Verified suppliers and manufacturers

Factory Price Conventional Fire Alarm System Lpcb and Ce Approved

Price $525.00
Min Order 1 Piece
Availability In Stock
Shipping From Guangdong, China
Popularity 556 people viewed
Model NO.:
AW-CFP2166
Type:
Fire Alarm
Anti-theft Alarm System Approach:
Active
Anti-Theft Alarm System Type:
Smoke Alarms
Anti-Theft Alarm System-Wide:
Wire Alarm Detectors
Anti-Theft Alarm System Distance:
Power Detector
Types of Smoke Detectors:
Photoelectric Smoke Style
Infrared Sensor Probe Type:
Inclination Sensor
Infrared Sensor Installation:
Ceiling
Combustible Gas Detector Model:
NA-300
Item:
Detection Control Panel
Zones:
1-32
Power Supply:
110VAC/240VAC
Battery:
12V2ah*2
Fire Relay Output:
Nc and No
Fault Relay Output:
Nc and No
Sounder Output:
2 Circuits
Fob Port:
Shenzhen
Delivery Time:
15 Days
Payment:
T/T, Western Union
Trademark:
Asenware
Transport Package:
EPE Inside, Carton Outside
Specification:
CE
Origin:
Guangdong, China
Product Description
1-32 zone conventional fire detection control panel

Introduction:

The AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard. And it is the central part of conventional fire alarm system, designed for applications requiring smoke detector, bell, manual pull stations, and sprinkler supervision. Each zone can be disabled by a button. The basic unit offers 1 to 8 zones of initiation, up to 16 zones for larger applications.




1 AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard.
2 It is modularized design, the panel can expend from 1 zone to 32 zones easily.
3 It has 2 level control mode by a lock
4 It has 24VDC and 5VDC power supply output.
5 It has FIRE and FAULT signal output.
6 It has 2 general sounders output.
7 Each zone has 1 circuit detectors input.
8 Each zone can be disable by a button.
9 It has RESET button to reset the panel.
10 It has SILENCE button to stop BUZZER and SOUNDERS.
11 It has EVACUATE button to start a manual fire alarm immediately.
12 It has battery low protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on.
13 It has an optional GSM module for fire alarm by SMS.
14 It is economic, user-friendly and easy maintenance.


Parameters:
ITEM1Zone panel2Zone panel4-8 Zone panel12-32 Zone panel
Model No.AW-CFP2166-01AW-CFP2166-02AW-CFP2166-04-8AW-CFP2166-12-32
Power specification
 
Mains supply voltage110VAC or 240VAC
Internal power supply27.2VDC
Total output current limited500mA @ 240VAC500mA @ 240VAC3A @ 240VAC3A @ 240VAC
Main supply monitor for faultYes
Battery protection for low voltageYes
Batteries (default configuration)12V2AH*2
Detector circuit specification
 
Number of circuit124-164-32
Line fault monitor for open circuitYes
Line fault monitor for short circuitYes
Line fault monitor for detector removalYes, if End of Line Monitor Unit fitted in place of End of Line Resistor
End of Line device6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Detector continuity diodesSilicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault)
Call point resistor value470 to 680 Ω, 0.225 or 0.5 watt
Maximum number of smoke/heat detectors per zone20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts.
Maximum number of manual call points per zoneNo limit
Sounder circuit specification
 
Number of general circuits2
End of line resistor value6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Line fault monitor for open circuitYes
Line fault monitor for short circuitYes
Outputs fused AT400mA
Maximum number of bells @ 20mA of each sounder output20
Fuses
 
Battery fuse1.5A F 20mm
Sounder outputs500mA F 20mm
Fire and fault output
 
Output typeNC and NO relay
Maximum current100mA
Connection block
 
Largest acceptable conductor size2.5mm2
Smallest acceptable conductor size0.75mm2
Size and weight
 

 
Dimensions(mm)272*200*70mm320*231*90mm395X502X124362X565X124
Weight (without batteries)4kg5kg7kg8kg
Weight (with batteries)5.8kg6.8kg9.6kg12.5kg