Hdr-60 Single Output DIN Rail Power Supply 60W 12V 4.5A, 15V 4A, 24V 2.5A

Price $7.80
Min Order 100 Pieces
Availability In Stock
Shipping From Zhejiang, China
Popularity 511 people viewed
Model NO.:
HDR-60
Output Type:
Single
Warranty:
2 Years
Output Power:
56~58W
Input Voltage:
AC88~264
Connection Mode:
Series Switching Power Supply
Starting Mode:
Self-excited Switching Power Supply
Voltage Regulating Mode:
Width Modulation Type
Power Supplying System:
Terminal Power Distribution Equipment
Energy Transmission:
One-way Transmission
Modulation System:
PWM
Certification:
CE, ISO, CCC
Brand:
Dhecn
Type of Output:
Single Output(AC/DC to DC),Constant Voltage
Type of Power Supply:
DIN Rail and Plastic Case Power Supply
Trademark:
DHECN
Transport Package:
45PCS/CTN
Specification:
ROHS, UL, CE, IEC, ISO9001
Origin:
UL, CE, Kc, ISO9001, RoHS
HS Code:
8504401990
Product Description
60W Single Output DIN Rail Power Supply
MODEL:HDR-60 Single Output Industrial DIN Rail Power Supply

Features:
·Universal AC input/ full range
·Protections: Short circuit/ Over load/ Over voltage
·Cooling by free air convection
·Can be installed on DIN rail TS-35/7.5 or 15
·solation class
·LED indicator for power on
·100% full load burn-in test
·1 year warranty
·Dimensions: 78*93*56mm (W*H*D)



casing No. : H033

MODEL

HDR-60-5

HDR-60-12

HDR-60-15

HDR-60-24

OUTPUT

DC Voltage

5V

12V

15V

24V

Voltage Tolerance

±2%

±1%

±1%

±1%

Rated Current

6.5A

4.5A

4A

2.5A

Current Range

0-6.5A

0-4.5A

0-4A

0-2.5A

Rated Power

32.5W

54W

60W

60W

Ripple & Noise

80mVp-p

120mVp-p

120mVp-p

150mVp-p

DC Adjustment Range

-5%,+10%

-8%,+10%

±10%

±10%

Setup, Rise Time

100ms,30ms/230VAC at full load200ms,30ms/115VAC at full load

Hold Time

100ms/230VAC23ms/115VAC at full load

INPUT

Voltage Range

88~264 VAC47~63 Hz;124~370VDC

AC Current

1.2A/115 V 0.8A/ 230 V

Efficiency

76%

82%

83%

81%

Inrush Current

Cold start 20A/115V 40A/230V

Leakage Current

<1mA/240VAC

PROTECTION

Over Load

105%~160%

Protection type: Constant current limiting, recovers automatically after fault condition is removed

Over Voltage

115%~135%

Protection type: Shut down o/p voltage, re-power on to recover

ENVIRONMENT

Working Temp., Humidity

-20ºC~+60ºC;20%~90 %RH

Storage Temp., Humidity

-40ºC~+85ºC;10%~95 %RH

Vibration

10~500Hz,2G 10min./1cycle, period for 60min, each along X, Y, Z axes

SAFETY

Withstand Voltage

I/P-O/P:3KVAC

Isolation Resistance

I/P-O/P:100M Ohms / 500VDC

STANDARD

Safety Standard

Design refer to UL60950-1,TUV EN60950-1,EN50178

EMC Standard

Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2,EN61204-3

OTHERS

Weight

0.3Kg

Packing

48pcs/15.4Kg/1.02CUFT

NOTE

1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″twisted pair-wire terminated with a 0.1μ & 47μ parallel capacitor.

3.Tolerance: includes set up tolerance, line regulation and load regulation.

4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.