Swipe or use the arrows to view product images.
High Quality 250kw 300kVA 400kw 500kVA Water-Cooled Gas Generator Set Generator for Natural Gas High Performance Biogas Plant
| Price | $35000.00 |
|---|---|
| Min Order | 1 Piece |
| Availability | In Stock |
| Shipping From | Sichuan, China |
| Popularity | 506 people viewed |
Model NO.:
WPG312B&NG
After-sales Service:
1 Year and Negotiable
Warranty:
1 Year and Negotiable
Output Type:
AC Three Phase
Gas Source:
Gas
Certification:
CE, ISO
Power:
>200kW
Standard:
Standard
Rated Voltage:
110V, 220V, 230V, 380V, 400V
Starting System:
24V DC Electric Start, 12V DC Electric Start
Frequency:
50/60Hz
Color:
Customizable
Engine Brand:
Weichai/Sdec/Yuchai/Googoi
Trademark:
JIWEI
Transport Package:
Wooden
Specification:
Customized
Origin:
China
Product Description
Power Supply-Professional Generator Set
In many industries, an uninterrupted power supply is essential to maintaining critical functions, so backup, emergency or backup power systems are indeed integral to ensuring continuity and reliability of operations. These systems serve as lifelines during unplanned outages, natural disasters or routine maintenance, protecting sensitive operations and preventing potential crises.
In short, a backup, emergency, or backup power system is a mandatory investment for any operation where uninterruptible power is mission-critical. This is a proactive measure to deal with power outages, which not only guarantees economic benefits, but also security and welfare.
In short, a backup, emergency, or backup power system is a mandatory investment for any operation where uninterruptible power is mission-critical. This is a proactive measure to deal with power outages, which not only guarantees economic benefits, but also security and welfare.
| Model | WPG312B(L)8NG |
| Prime Rating kVA/kWe | 312/250 |
| Continual Rating kVA/kWe | 250/200 |
| Voltage V | 400/230 |
| Frequency Hz | 50 |
| Power Factor | 0.8(lagging) |
| No. of Phases | 3 |
| Sound@7m(dB·(A)) | Open:≤99 dB(A);Silence:≤85 dB(A) |
| Ambient temp(°C) | -10~40(If <-10, oil and water heating; If >40, power correction) |
| Altitude(m) | ≤1000 |
| Fuel | Pipeline natural gas;MN≥85 |
| Gas supply pressure(kPa) | Max. inlet 50 (Special pressure, contact with company) |
| Steady-state voltage deviation | ≤±2.5% |
| Transient voltage deviation (100%sudden power decrease/increase) | +25%~-20% |
| Voltage steady time(s) | 2 |
| Transient frequency deviation from rated frequency (100% sudden power decrease/increase) | ≤1.5% |
| Gen-set regulation class | ±18% |
| Frequency steady time(s) | 15 |