Menu
Global B2B sourcing platform
Verified suppliers and manufacturers

High Voltage Electric Outdoor Automatic Circuit Recloser Medium Voltage for Switchgear

Price $1799.00
Min Order 1 Piece
Availability In Stock
Shipping From Zhejiang, China
Popularity 482 people viewed
Breaking Capacity:
High Voltage Circuit Breakers
Operation:
Manual Type
Speed:
Normal Type Circuit Breaker
Arc-extinguishing Medium:
Vacuum
Installation:
Fixed
Structure:
Recloser
Poles Number:
3
Type:
Circuit Breaker
Function:
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection)
Certification:
ISO9001-2000, CE, CCC
MOQ:
1PCS
Trademark:
KODERY
Transport Package:
Normal Export Case
Specification:
2465*500*2400
Origin:
China
HS Code:
8537209000
Product Description
Product Description

ZW7-40.5 type outdoor high voltage vacuum circuit breaker is the three-phase AC 50Hz outdoor high voltage electrical equipment, suit for control and protection of 20-40.5kV transmission and distribution systemcan also be used for sectional circuit breaker and switching capacitor bank occasions; this product can be matched with piecewise controller, reclose device can realize the power system intelligent segmentation, reclose control. And can add the current transformer for measurement and protection. Circuit breaker equipped with spring or electromagnetic actuator, reliable mechanical performance, frequent operation; no fire and explosion dangercircuit breaker conforms to the national standard GB19841989 "AC high voltage circuit breaker" and the International Electrotechnical Commission Standard IEC56, IEC62271-100 "high voltage AC circuit breaker" requirements.

Product Parameters
ItemUnitParameter
Voltage, current parameters  
Rated voltagekV40.5 
Rated short time power frequency withstand voltage (Imin)kV95
Rated lightning impulse withstand voltage (peak)kV185
Rated currentA1250, 1600, 2000
Rated short-circuit breaking currentkA25, 31.5
Rated operating sequence O-0.3s-CO-180s-CO
Rated short-circuit current breaking timestimes12
Rated short-circuit closing current (peak)kA63.80
Rated peak withstand currentkA63.80
Rated short-time withstand currentkA25, 31.5
Rated short-circuit current durationS4
Average opening velocityms1.5±0.2
Average closing speedms0.7±0.2
Contact closing bounce timems<5
Three-phase close (open) synchronization errorms<2
Closing timems<150
Opening timems<60
Mechanical lifetimes10000
Rated operational voltage and auxiliary circuits rated voltageVDC220, AC220
DC resistance of circle every phase (not including transformer)μΩ<100
Dynamic, static contact allowed to wear thicknessmm3
Weightkg800
Detailed Photos

Company Profile

  • Similar Products
Full Page Contact Supplier