Menu
Global B2B sourcing platform
Verified suppliers and manufacturers

Zn63-12 Indoor High Voltage Solid Vacuum Circuit Breaker Embedded Pole Vcb with Handcart

Price $2000.00
Min Order 1 Piece
Availability In Stock
Shipping From Zhejiang, China
Popularity 427 people viewed
Model NO.:
ZN63-12
Breaking Capacity:
High Voltage Circuit Breakers
Operation:
Energy-storage Type
Speed:
Normal Type Circuit Breaker
Arc-extinguishing Medium:
Vacuum
Installation:
Fixed or Handcart Type
Structure:
Vcb
Poles Number:
3
Type:
Indoor Vacuum Circuit Breaker
Function:
Isolation,Protection,Automatic Reclosing
Certification:
ISO9001-2000
Rated Voltage:
12kv
Rated Current:
630/1250/1600A
Mechanical Life:
30000 Times
Altitude:
1000m
Trademark:
ZGHQDL
Transport Package:
Wooden Box Packing
Specification:
Custom-made
Origin:
China
HS Code:
8535210000
Product Description
ZN63-12 Indoor High Voltage Vacuum Circuit Breaker (Modular) is our latest medium-voltage vacuumcircuit breaker product, which is
suitable for air-insulated indoor switching systems. The circuit breakeradopts the new solid-sealed pole technology with a modular
mechanism. At the same time, the circuitbreaker has perfect mechanical and electrical interlocking functions, and can be widely used
in energy.industry, construction, infrastructure and other fields.
The circuit breaker can perform frequent operation within the operating current range or open the shortcircuit current multiple times;
The mechanical life can be up to 30,000 times, and the number offullcapacity short-circuit current breaks can reach 50 times.
Circuit breakers are suitable for reclosing operations and offer high operational reliability and servicelife.
The circuit breaker can be installed in the switchgear ither as fixed or withdrawable or mounted on aframe.

No.ItemUnitData
1Rated voltageKV12
2Max.working voltageKV12
3Rated currentA630 1250630 1250 1600  2000 2500  31501250  1600 2000 2500 3150  4000
4Rated short circuit breaking current (Rated thermal stability current (RMS))KA20/2531.540
5Rated short-circuit current (peak)KA50/6380100
6Rated dynamic stability current (peak)KA50/6380100
74S Rated withstand currentKA20/2531.540
8Rated insulation levelPower frequency withstand voltage (rated breaking before and after)/1 min power frequency withstand voltageKVTo earth 42 (Between open contacts)
Impulse withstand voltage(rated breaking before and after)/Lightning impulse withstand voltage (peak)To earth 75 (Between open contacts
9Rated thermal stability timeS4
10Rated operating sequence O-0.3S-CO-180S-CO
11Mechanical lifeTimes20000
12Rated short circuit current breaking timeTimes50
13Rated operating mechanism closing voltage (DC)VAC,DC    110,220
14Actuator voltage of the floodgate (DCVAC,DC    110,220
15Contact strokemm11±1
16Overtravel(the length of contact spring compression)mm3.5±0.5
17Three-phase points,closing phase asynchronousMs≤2
18Contact closing bounce timems≤2
19Average opening speedm/s0.9~1.2
Average closing speedm/s0.5~0.8
20Opening timeUnder max.operating voltageS≤0.05
21Under min.operating voltage≤0.08
22Closing timeS0.1
23The main circuit resistance of each phaseμΩ630≤50  1250≤45
24Allowed comision thickness for fixed and movable contactsmm3

  • Similar Products