Zn63 (VS1) -12 Side Mounted Vacuum Circuit Breaker

Price $1900.00
Min Order 1 Piece
Availability In Stock
Shipping From Zhejiang, China
Popularity 280 people viewed
Model NO.:
ZN63(VS1)-12
Breaking Capacity:
High Voltage Circuit Breakers
Operation:
Manual Type
Speed:
Normal Type Circuit Breaker
Arc-extinguishing Medium:
Vacuum
Installation:
Fixed
Structure:
Zn63(Vs1)-12
Poles Number:
3
Type:
Circuit Breaker
Function:
Conventional Circuit Breaker
Certification:
ISO9001-2000, IEC
Trademark:
JECSANY
Transport Package:
Wooden Carton
Specification:
ZN63(VS1)-12 Side-Mounted Circuit Breaker
Origin:
China
HS Code:
8504220000
Product Description

ZN63(VS1)-12 Side-Mounted Circuit Breaker 


ZN63(VS1)-12 indoor high voltage vacuum circuit breaker applies to power system of rated voltage 12kv as a protective and control unit for power grid equipment and industrial power equipment It can equip with KYN28(GZS1), XGN, GG-1A and other types of switchgear panels. Related products: isolated handcart, fuse handcart and voltage transformer handcart.


standards
ZN63(VS1) indoor high-voltage alternating-current vacuum circuit breaker is produced in line with the following standards and codes.
IEC 62271-100 High-voltage alternating-current circuit-breakers.
GB/T 11022-2011 Common specifications for high-voltage switchgear and controlgear standards.
GB 1984 High-voltage alternating-current circuit-breakers.
GB 311.1 lnsulation co-ordination for high voltage transmission and distribution equipment.

Applying ambient condition

Ambient temperature:-10ºC-+40ºC
Relative humidity:The average humidity of a day should be no more than 95%. The average humidity of a month should be no more than 90%.
Earthquake intensity: not exceed 8 degrees.
Saturated vapor pressure the average pressure of a day should be no more than 2.2kPa; the average pressure of a month should be no more Than1.8Kpa;
The height above sea level:1000 m (Except special requirements)
It should be installed in the places without fire, explosion, serious filth, and chemical erosion and violent vibration.
 
Product Parameters
 
ItemUnitData
Rated voltagekV12

Rated insulation level
1min power frequency voltagekVTo earth/Phase to Phase 42/48
Lightning impulse withstand voltage(peak )kATo earth/Phase to Phase 75/85
Rated short-circuit breaking currentkA2025 
Rated currentA630630 
12501250 
Rated frequencyHz50
Rated short-circuit withstand current
kA
20 
Rated peak withstand current50 
Rated short-circuit closing current(peak)50 
Duration of rated short circuit currentS4
Mechanical lifetimes1000
Frequency tolerance of the secondary circuit voltage(1min)V2000
Rated operating squence O-t-CO-t1-CO

Overall dimension: