High-voltage
                        High Voltage Power Transmission, Insulation, Driving, Electrical Installation
                        Trough Type
                        IEEE
                        Black
                        Rib or OEM
                        Crosslinking
                        EPDM
                        200A
                        3 in Dia X 11 in L
                        35 Kv
                        RIB
                        Pallet
                        Jiangsu
                        8538900000
                        
                        Product Description
                    
                                | Type | AC Withstand Voltage (1 min) | Basic Impulse Level | Corona Extinction (3pC) | Current Rating | kV Class | 
| Bushing Insert | 50KV | 150KV | 26KV | 200A | 35KV | 
The Loadbreak Bushing Insert meets all the requirements of IEEE Standard 386, and is fully interchangeable with competitor's products and mating products that also meet IEEE Standard 386. When installed with mating components, the bushing insert provides a fully shielded and fully submersible connection for loadbreak applications.
 - Meets or Exceeds IEEE Std. 386 and IEEE Std. 592 requirements
 
- Interchangeable with other products meeting the same requirements
 
- Fully shielded, insulated and submersible
 













                    







  
  Audited Supplier
 