Technical Data For Single Phase Pole Mounted Transformer Conventional Type | |||||
Rate power | High voltage | Low voltage | No load losses(w) | On load losses(w) | Weight(kg) |
10kva | 34500/19920V 13800/7957V 13200/7620V 12470/7200V or others | 120-240V 240-480V 347V 600V | 36 | 120 | 150 |
15kva | 50 | 195 | 210 | ||
25kva | 80 | 290 | 258 | ||
37.5kva | 105 | 360 | 340 | ||
50kva | 135 | 500 | 395 | ||
75kva | 190 | 650 | 480 | ||
100kva | 210 | 850 | 583 | ||
167kva | 350 | 1410 | 680 |
Technical Data For Single Phase Pole Mounted Transformer CSP Type | |||||
Rate power | High voltage | Low voltage | No load losses(w) | On load losses(w) | Weight(kg) |
10kva | 34500/19920V 13800/7957V 13200/7620V 12470/7200V or others | 120-240V 240-480V 347V 600V | 50 | 120 | 150 |
15kva | 65 | 195 | 205 | ||
25kva | 105 | 290 | 245 | ||
37.5kva | 140 | 360 | 335 | ||
50kva | 180 | 500 | 370 | ||
75kva | 250 | 650 | 505 |
These transformers also used for small substation, miscellaneous applications and can serve to step up voltages.Daelim designs and produces single phase in two types: single phase pole mounted conventional transformer and completely self protected(CSP) transformer. Power rating up to 167kVA.
Daelim's single-phase fully complies with or even exceeds international standards such as ANSI/IEEE, CSA, and DOE. Single-phase has ul/cul, CSA, IEEE and other certificates. It has been exported to North America, Central and South America and other markets in large quantities.

Except from some similarities such as cylinder tank, hooks, lifting lugs, grounding devices, nameplates, core and winding with the conventional type. This type of transformers have characteristics and devices as follows:
1) One or two high voltage bushings are on the cover with fuse.
2) One or two arresters are installed on the wall of the tank, whose top end is near to the high voltage bushing, and connected to the bushing by a copper strip. One secondary breaker switch is above the winding inside the tank, and here are operating handle,overload reset and signal light.
3) Low voltage bushing is educed from the wall of the tank, grounding device is fixed to position X2. One end of the single
bushing leads out through the high voltage bushing, the other end is ground connection.
4) All units are built in accordance with ANSI/IEEEC57.12.20, CSA C2.1-06,CSA C2.2-06 and etc.