Through-put rating up to 160 MVAr


| 1.1.1 GENERAL TECHNICAL DATA | ||
| Highest voltage | 36kV | 50Hz |
| Operating voltage | 33 kV±5% | 50Hz |
| Voltage for aux. drivers | 380V | 50Hz |
| Control voltage | 220V | 50Hz |
| Interlock voltage | 220V | 50Hz |
| PLC signals | 24V | DC |
| Ambient temperature max./min. | 45 / - 10 | Deg. C |
| Altitude | 1500 | m |
| Humidity | 80 | % |
| 1.1.2 TRANSFORMER DATA | ||
| Operating voltage | 33kV±5% | |
| Frequency | 50Hz ±1% | |
| Operation | Continuously | |
| EAF transformer rated capacity | MVA (+ 20% Overload) | |
| Rated current | 2449.4 A (+ 20% Overload) | |
| Reactor Rated Power | 18 MAVR (25.92 MVA Overload) | |
| Reactance in normal tap | 1 Ω | |
| Number and ratio of taps | 6 taps: 100%-80%-60%-40%-20%-0 | |
| Insulation level Winding: Um: AC: BIL: | Full insulation HV 52 kV 95 kV 250 kV | |
| Protection level | IP54 | |
| Vector group | III | |
| System short circuit capacity | 1500 MVA | |
| Short circuit duration | 6 sec | |
| Short circuit times | 2.5 times | |
| Regulation method | Off circuit | |
| Type of tap changer | NLTC Off -circuit motor drive | |
| Manufacturer | Shanghai Huaming / China (ZUNYI) | |
| Model | 2*ZWL III-1600/40- 6 taps | |
| Number of taps | 6 | |
| Reactor Winding Materials | Copper | |
| Cooling Type | OFWF | |










Audited Supplier