The rated capacity of this pad mounted transformer is 2500kVA(2.5MVA). It is usually used outdoors
The models that can be selected for oil immersed transformers include S9, S11, S13, S15, and so on.
The high-voltage part of oil immersed transformers can also be selected from 6KV, 6.3KV, 10KV, 10.5KV, 11KV, 20KV, 25KV, 33KV, 35KV, and so on
The low voltage part of oil immersed transformers can also be selected: 400V, 415V, 0.4KV, etc. It can be configured according to the actual situation in your local area.
2500kVA(2.5MVA) Pad mounted transformer appearance


2.5 MVA Pad Mount Transformer | ||||
NO. | Particulars | Unit | Specification | Remark |
1 | Type | ~ | pad mounted, radial feed | step down |
2 | Rated capacity | KVA | 2500 | |
3 | No. of Phase | ~ | 3 | |
4 | Primary voltage | V | 34500 Delta (customization) | |
5 | Primary connection | ~ | 35kV class, 600A bushing | |
6 | Secondary voltage | V | 415Y/240 Wye-N (customization) | |
7 | Secondary connection | ~ | 10-hole spade | |
8 | Tapping type | ~ | off-circuit tapping | |
9 | Tapping range | % | ±2*2.5% (customization) | |
10 | Cooling method | ~ | ONAN | |
11 | Rated frequency | HZ | 50 (customization) | |
12 | Vector group | ~ | Dyn11 (customization) | |
13 | Insulation class | ~ | A | |
14 | Temperature rise | K | 65/60(winding/top oil) | |
15 | Off-load loss | W | 2780 | 10% tolerance |
16 | On-load loss (85ºC) | W | 26500 | |
17 | Impedance | % | 5.5~8 | |
18 | Winding material | ~ | Copper/Aluminum | |
19 | Core material | ~ | silicon steel | |
20 | Cooling material | ~ | mineral oil | |
21 | Housing material | ~ | 304 Stainless Steel (customization) | IP65 |
22 | Service condition | ~ | outdoor | |
23 | Sea level | M | ≤1000 | |
24 | Standard | ~ | IEC60076 |
(↓If you have other product needs, please click here to ask me)

The iron core is made of brand new and excellent silicon steel sheets.
Ensure that customers maintain low wear and tear during use, low noise during operation, and more energy-efficient requirements

Use heat-resistant enameled wire.
Ensure good conductivity, stable operation, enhanced overload capacity, low line loss, and resistance to oxidation of the winding.
Extend the lifespan of transformers

The transformer oil tank is composed of corrugated walls that can breathe.
Excellent corrugated walls can compensate for changes in transformer oil volume caused by temperature rise and fall. Therefore, we cancelled the design of the oil storage tank for the transformer. This not only reduces the cost of the transformer, but also lowers the overall height of the transformer. Saved users' various costs.

We will equip the transformer with sensitive relief valves and precise glass thermometer sockets.
Of course, we can also equip trip terminals with alarms and gas relays according to customer requirements.
Everything is just to ensure your safety during use.

Four production workshops
Due to the independent control of all aspects of our company, we can achieve economic benefits for our products. We ensure that each product is not only of high quality, but also very cheap.