AISIKAI MCCB Normal working conditions and installation methods | |
Category | Requirements |
Elevation | Installation site not exceeding 2000 meters above sea level |
Ambient air temperature | The upper limit does not exceed+ 40 ºC; the lower limit does not exceed - 5 ºC; the average value of 24 hours does not exceed + 35 ºC |
Pollution Level | Level 3 |
Installation Category | Installation Category Ill, Circuit Breaker 1600A IV |
Atmospheric conditions | Atmospheric relative humidity does not exceed 50% when the ambient air temperature is + 40 C. It can have a higher relative humidity at a lower temperature. The average maximum relative humidity of the wettest month is 90%, and the average minimum temperature of the month is + 25 C. Considering the condensation occurring on the surface of the product due to temperature changes. |
Installation Conditions | Installed in places without significant shaking and shock vibration, the magnetic field near the installation site should not exceed 5 limes of the magnetic field in any direction, and leakage circuit breakers should generally be installed vertically. |
Installation | Circuit breaker can be installed vertically (i.e. vertically) or horizontally (i.e. horizontally). |
Input mode | Circuit breaker can't go down, that is, only 1,3,5 power lines, 2,4,6 load lines |

Circuit breaker with overload, short circuit and under voltage protection device to protect the power lines and equipment from damage.
The circuit breaker can be installed vertically (ie, vertical loading), or horizontally (ie, cross-loaded).
Rated insulation voltage 800V,suitable for AC 50HZ, rated working voltage 690V and below the circuit for infrequent start with.

Model | ASKM1-63 | ASKM1-125 | ASKM1-250 | ASKM1-400 | ASKM1-630 | ASKM1-800 | ASKM1-1600 | ||||||||||||
Frame rating current Inm(A) | 63 | 125 | 250 | 400 | 630 | 800 | 1600 | ||||||||||||
No. of poles | 3P/4P | 3P/4P | 3P/4P | 3P/4P | 3P/4P | 3P/4P | 3P/4P | ||||||||||||
Rated current In(A) | 10 16 20 25 32 40 50 63 | 16 20 25 32 40 50 63 80 100 125 | 100 125 140 160 180 200 225 250 | 225 250 315 350 400 | 400 500 630 | 630 700 800 | 800 1000 1250 1600 | ||||||||||||
Rated insulation voltage Ui(V) | 1000V | ||||||||||||||||||
Rated impulse withstand voltage Uimp(V) | 12000V | ||||||||||||||||||
Rated operational voltage Ue(V) | AC400V/415V AC660V/690V | ||||||||||||||||||
Arc distance (mm) | 50(0)** | 50(0)** | 50(0)** | 100(0)** | 100(0)** | 100(0)** | 100(0)** | ||||||||||||
Breaking capacity level | L | M | H | L | M | H | L | M | H | L | M | H | L | M | H | M | H | M | |
Ultimate short-circuit breaking capacity Icu(kA) | AC400V/415V | 25 | 35 | 50 | 35 | 50 | 65 | 35 | 50 | 65 | 50 | 65 | 100 | 50 | 75 | 100 | 85 | 100 | 85 |
AC660V/690V | 10 | 12 | 12 | 12 | 20 | 20 | 12 | 20 | 20 | 15 | 20 | 20 | 20 | 30 | 30 | 20 | 30 | 20 | |
Service short-circuit breaking capacity Ics(kA) | AC400V/415V | 18 | 22 | 35 | 22 | 35 | 50 | 25 | 35 | 50 | 35 | 50 | 65 | 35 | 65 | 75 | 75 | 85 | 65 |
AC660V/690V | 10 | 12 | 12 | 12 | 20 | 20 | 12 | 20 | 20 | 15 | 20 | 20 | 20 | 30 | 30 | 20 | 30 | 20 | |
Use category | A | A | A | A | A | A | A | ||||||||||||
1) Electrical service life(times of operation) | AC400V/415V | 8000 | 8000 | 8000 | 7500 | 7500 | 7500 | 5000 | |||||||||||
AC660V/690V | 1500 | 1500 | 1000 | 1000 | 1000 | 500 | 500 | ||||||||||||
1) Mechanical service life(times of operation) | without maintenance | 20000 | 20000 | 20000 | 10000 | 10000 | 10000 | 8000 | |||||||||||
with maintainable | 40000 | 40000 | 40000 | 20000 | 20000 | 20000 | 16000 | ||||||||||||
Outline dimensions (mm) | W(3P/4P) | 78/101 | 92/122 | 107/142 | 150/198 | 182/240 | 210/280 | 210/330 | |||||||||||
L | 130 | 150 | 165 | 257 | 270 | 280 | 280 | ||||||||||||
H(including handle) | 90 | 88 | 112 | 155 | 160 | 160 | 197.5 |




AISIKAI MCCB DIMENSION SHEET | |||||||
Dimension | M1-63L | M1-63M | M1-125L/M | M1-125H | M1-250L/M | M1-250H | M1-250L/M |
Overall Dimensions | C | 85 | 85 | 87.5 | 87 | 102 | 102 |
E | 51 | 51 | 55 | 55 | 55 | 55 | |
F | 22 | 22 | 22 | 22 | 22 | 22 | |
G | 14 | 14 | 17.5 | 17.5 | 23 | 23 | |
G1 | 6.5 | 6.5 | 7.5 | 7.5 | 11.5 | 11.5 | |
H | 76 | 76 | 73 | 90 | 89 | 106 | |
H1 | 90 | 100 | 87 | 105 | 112 | 127 | |
H2 | 18.5 | 18.5 | 24 | 24 | 23 | 23 | |
H3 | 8 | 8 | 8.5 | 9 | 7 | 7 | |
L | 136 | 136 | 150 | 150 | 166 | 166 | |
L1 | 170 | 170 | 255 | 255 | 292 | 292 | |
L2 | 118 | 118 | 131 | 131 | 144 | 144 | |
W | 78 | 78 | 92 | 92 | 106 | 106 | |
W1 | 25 | 25 | 30 | 30 | 35 | 35 | |
Mouting Dimensions | A | 25 | 25 | 30 | 30 | 35 | 35 |
B | 117 | 117 | 129 | 129 | 129 | 126 | |
Φd | 4.5 | 4.5 | 4.5*6 | 4.5*6 | 4.5*6 | 5.5 |


Before we received the first order, please afford the sample cost and express fee.
AISIKAI will return the sample cost back to you within your first order.
B) Sample time?
Existing items: Within 3 days.
Yes. We can print your Logo on both the products and the packages if you can meet our MOQ.
D) What's about MOQ? Delivery time ?
1pcs for ATS. Normally less than 1000A MCCB with stock, quick support.
E) How to guarantee the quality of your products?
1) Strict detection during production one by one.
2) Strict inspection on products one by one before shipment and intact product packaging ensured.