SPECIFICATIONS
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained
during cranking.
MAXIMUM OPERATING CURRENT
100 mA at 12 V, 105 mA at 24 V
MAXIMUM STANDBY CURRENT
60 mA at 12 V, 55 mA at 24 V
MAXIMUM SLEEP CURRENT
40 mA at 12 V, 35 mA at 24 V
DIGITAL INPUTS A to F
Negative switching
ANALOGUE INPUT A
Configurable as:
Negative switching digital input
0 V to 10 V
4 mA to 20 mA
0 Ω to 240 Ω
ANALOGUE INPUTS B to D
Configurable as:
Negative switching digital input
0 Ω to 480 Ω
FREQUENCY RANGE
3.5 Hz to 75 Hz
ELECTRO-MAGNETIC COMPATIBILITY
EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment
ELECTRICAL SAFETY
Safety of Information Technology Equipment,
including Electrical Business Equipment
TEMPERATURE
Ab/Ae Cold Test -30 oC
BS EN 60068-2-2
Bb/Be Dry Heat +70 oC
VIBRATION
Ten sweeps in each of three
major axes
5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn
HUMIDITY
Db Damp Heat Cyclic 20/55 oC
@ 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 oC
@ 93% RH 48 Hours
SHOCK
Three shocks in each of three major axes
15 gn in 11 mS
DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
IP65 - Front of module when installed into the control panel with the supplied sealing gasket.