This linkage type fire alarm controller mainly to be used in middle and big size fire fighting project. It is the fire fighting master.





Features:
★ Capacity of the panel:
Number of loop: 4
Max.addressable points: 1024
Manual control panel: 1(8 loop output, including 1 loop special output of sound and light alarm)
★240*64 LCD displays key information and indicators for showing key status in Chinese or English.
★Convertible between Chinese and English , comform to internationalization.
★Print information function for Chinese and/or English.
★One pair of passive connector for common alarm, one for common fault connector output
★CANBus interface, zone CIE to connector other equipment by LD6900 communication module.
(CANBusRS232, RS485, Ethernet, Telephone line, GPRS).
★On-scene data set by CIE and/or SD card.
★Black-box function, data storage up to 1000 fire alarm records, 1000 gas extinguishing records and 1000 pieces of relevant information.
★External equipment can be controlled using either the BUS or multi-line panel.
★Short circuit protection in the loop an power supply.
★Addressing of field devices randomly.
★Alarm supervisory function.
Main technology specifications:
| Content | Technical Data |
| Power supply voltage | AC 220V(187V-242V)50Hz |
| Output voltage to the loop | DC14V~24V |
| Output to the panel | DC24V/4A |
| Number of loop | 4 |
| Number of output connector | 8 loop(including one loop sound and light) connected output. One pair of passive connector for common alarm. One for common fault |
| Max. Number of addressable codes | 1024(single loop total number of address: 256) |
| Max. Output current to the loop | 200mA |
| Max. Protection current for short-circuit | 400mA |
| Unload power | ≤ 5W |
| Operating temperature | 0ºC~45ºC |
| Relative humidity | ≤ 95%RH(40±2ºC) |
| Mounting method | Wall-mounted |
| Battery | 2*12V/14Ah |
| Max. External dimension | 510(W)mm×155(D)MM×650(H)mm |
| Weight | 14.20kg ± 0.1kg(Excluding battery) |