Product Features:
· Highly efficient and stable components from internationally recognised brands
· Efficient thermal system design reduces risk of overheating, increasing lifespan
· Advanced MPPT (Maximum Power Point Tracking) algorithms MPPT efficiency >99.9%
· High performance index with wide power range
· Anti-islanding technology
· Advanced, highly reliable system protection
· Built-in isolated transformer, suitable for varied PV applications
· LCD display with wide range of features and language options
· Easy to install, operate and maintain
· Passed multiple stringent performance tests
· Suitable for indoor and outdoor installations
| Inverter model | AVE-1000KTL | |
| PV side | ||
| Max. PV power | 1100kWp | |
| Max. permitted DC Voltage | 880Vdc | |
| Isc PV Current | 3000A | |
| Max. permitted DC current | 2400A(32*75A) | |
| String number | 32 | |
| MPPT range | 450~820Vdc | |
| PV Start Voltage | 465Vdc | |
| MPPT efficiency | 99.9% | |
| Max Inverter feedback Current to the Array | 0A | |
| Grid side | ||
| Rated output power | 1000kW | |
| Max.output current | 2140A | |
| THD of grid current | <3% | |
| Power factor(cosφ) | >0.99 | |
| Max. degree of efficiency | 98.1% | |
| European deg. of efficiency | 97.6% | |
| Normal output voltage | 270 Vac 3~ | |
| Operation grid frequency | 47.5~51.5Hz | |
| Standby power Consumption | <200W | |
| Nighttime Power Consumption | <100W | |
| Grid monitoring | According to VDE0126-1-1 guidelines | |
| communication interface | RS485/Ethernet(optional)/GPRS(optional) | |
| Man-machine interface | LCD touch screen | |
| Mechanical | ||
| Dimensions (W × H × D) | 4900mm×2120mm×800mm | |
| Weight | 4000Kg | |
| Environmental conditions and safety | ||
| Ingress protection | IP20 | |
| Protective class | I | |
| Cooling | Air cooling | |
| Operating temperature range | -25~+55'C | |
| Relative humidity range | 15-95% (non condensing) | |
| Altitude | 2000m;above 2000m need derate operating | |
| Noise emissions | <65dB | |
| Meet the standards | EN 50178;DIN EN 62109-1; prlEC 62109-2; VDE 0126-1-1(or CGC/GF001:2009); EN6100-6-2 2005; EN6100-6-4 2007; ENEL(Italy);  | |



  
  Audited Supplier
 