| Electrical data (Ta=25ºC±5ºC) |
| Type | B2N- 0.5A | B2N- 1A | B2N- 2A | B2N- 5A | B2N- 10A | B2N- 20A | Unit |
| Rated current(Ipn) | 0.5 | 1 | 2 | 5 | 10 | 20 | A |
| Measure range(Ip) | 1 | 2 | 4 | 10 | 20 | 30 | A |
| Turns ratio(Np/Ns) | 30:1500 | 15:1500 | 8:1600 | 3:1500 | 2:2000 | 1:2000 | T |
| Internal resister | 400 | 400 | 400 | 400 | 400 | 400 | Ω |
| Rated output | @Ip=±Ipn ±4±0.5% | V | |||||
| Supply voltage | ±12,±15 | V | |||||
| Power Consumption | ≤20+ IpX(Np/Ns) | mA | |||||
| Zero offset voltage | @Ip=0 ≤±20 | mV | |||||
| Offset voltage drift | @ -40~+85ºC ≤±0.5 | mV /ºC | |||||
| Linearity | @Ip=0-±Ipn ≤0.1 | %FS | |||||
| Response time | @100A/μ S,10%-90% ≤1 | μS | |||||
| Galvanic isolation | @ 50HZ,AC,1min 2.5 | KV | |||||
| Applications |
·AC variable speed drives
·Static converters for DC motor drives
·Battery supplied applications
·Uninterruptible Power Supplies (UPS)
·Switched Mode Power Supplies (SMPS)
·Power supplies for welding applications


| Current | d | Connected | Terminal PIn Identification | |
| 1 | 0.5A-3A | 2-ø0.6 | 5,10 | 1...+15V 2...-15V 3...0V 4...Output 5.6,7...primary input current(+) 8,9,10...primary input current(-) |
| 2 | 5A,10A | 2-ø0.6 | 6,9 | |
| 3 | 20A | 4-ø1.6 | 6-7,8-9 |
1. All dimensions are in mm.
2. General tolerance ±1mm.
| Directions for use |
1. When the current will be measured goes through a sensor, the voltage will be measured at the output end. (Note: The false wiring may result in the damage of the sensor)
2. Custom design in the different rated input current and the output voltage are available.
| Standards |
·EN60947-1:2004
·IEC60950-1:2001
·EN50178:1998
·SJ 20790-2000
| General date |
| Value | Unit | |
| Operating temperature(TA) | -40 to +85 | ºC |
| Storage temperature(TS) | -40 to +125 | ºC |
| Mass(approx) (M) | 22 | g |