HITACHI DC INVERTER SCROLL COMPRESSOR
CONDENSER AND EVAPORATOR:SPECIALLY DESIGNED CONTROL SYSTEM FOR DC INVERTER WATER SOURCE HEAT PUMP:
AirValley is a heat pump manufacturer focusing on OEM and ODM. We have excellent R&D engineers and cooperate with excellent components manufacturers to provide customers with cost-effective products, and can provide customized services according to customer requirements.

Advanced Production Line

Work flow chart

The cooperation of Dan-foss & AirValley

Advanced Laboratory
-35ºC 15HP heat pump performance laboratory Dan-foss laboratory in Haiyan China

DC Inverter Water Source Heat Pump Water Heater - R410A | |||||||
Model | / | DWRS-47II | DWRS-95II | DWRS-120II | DWRS-190II | DWRS-240II | |
Horse Power | HP | 12 | 25 | 30 | 50 | 60 | |
Rated heating capacity | KW | 47 | 95 | 120 | 190 | 240 | |
Rated power | KW | 9.78 | 19.57 | 25.25 | 38.92 | 50.11 | |
Rated current | A | 18.57 | 37.17 | 47.96 | 73.92 | 95.17 | |
Maximum power | KW | 15.75 | 27.25 | 34.22 | 53.56 | 67.58 | |
Maximum current | A | 29.91 | 51.75 | 64.99 | 101.72 | 128.35 | |
Performance coefficient | COP | 4.81 | 4.85 | 4.75 | 4.88 | 4.79 | |
Rated hot water produce capacity (Delta T = 40) | L/H | 1011 | 2042.5 | 2580 | 4085 | 5160 | |
Rated hot water output tempemperature | ºC | 55 | |||||
Maximum hot water output temperature | ºC | 60 | |||||
Heat source side inlet temperature working range | ºC | 8~30 | |||||
Power supply | 3N 380V~420V/50Hz | ||||||
Compressor | Type | DC Inverter type | |||||
Brand | Hitachi | ||||||
Driver | Cooling type | Refrigerant-cooled | |||||
Hot water side heat exchanger | Type | Shell & Coil Heat Exchanger | |||||
Water flow | M3/h | 8.1 | 16.3 | 20.6 | 32.7 | 41.3 | |
Water pressure drop | KPa | ≤60 | ≤70 | ≤70 | ≤70 | ≤70 | |
Pipe connection | DN | DN40 | DN50 | DN65 | DN65 | DN65 | |
Pipe type | Outer thread | ||||||
Heat source side heat exchanger | Type | Brazed plate heat exchanger | Shell & Coil Heat Exchanger | ||||
Water flow | M3/h | 6.1 | 12.3 | 15.5 | 24.5 | 31.0 | |
Water pressure drop | KPa | ≤60 | ≤70 | ≤70 | ≤70 | ≤70 | |
Pipe size | DN | DN40 | DN50 | DN65 | DN65 | DN65 | |
Pipe connection | Outer thread | ||||||
Protections | 1. High and low pressure protection, 2. Anti-freeze protection, 3. High temperature protection, 4. Overload protection, 5. Reverse of phase protection, Lack of phase protection, etc. | ||||||
Refrigerant | Type | R410A | |||||
Quantity(KG) | 7.2 | 7.2x2 | 7.4x2 | 7.2x4 | 7.4x4 | ||
Noise | ≤DB(A) | 48~65 | 50~67 | 51~68 | 53~74 | 54~75 | |
Weight | KG | 220 | 480 | 580 | 850 | 950 | |
Unit dimensions | MM | 1050x840x800 | 1650x1050x1200 | 2000x1100x1250 | |||
Note: 1. Hot water heating standard condition: Hot water side initial water temperature 15ºC, final water temperature 55ºC; Heat source side water input temperature 15ºC. | |||||||
2. The above parameters are based on refrigerant R410A, for parameters based on other refrigerant please contact us. |
1.The best product price;
2.Priority production arrangements;
3.Rich product training;
4.First-hand new product consultation;
5.Free brochure design;
6.More timely email reply and so on.
During the warranty time, we can supply free spare parts if any problem casued by AirValley.
Water to water heat pump, Geothermal heat pump, Air to water heat pump, Air source heat pump, Heat pump water heater, DC Inverter heat pump, Water source heat pump