* Reliable protection at high ambient temperatures
* Loadable: String protection up to
125 size: 63A, 80A, 100A, 125A
400Size: 320A, 400A
630Size: 630A, 800Size: 800A
1250Size:1000A 1250A
1600Size:1600A
* Tasted: Ultimate short circuit breaking capacity lcu of 25kA according to IEC IEC60947-2
* Fast: reclosable for minmum standstill times
* Safe: reliable disconnector properties, switching under load
* Approval: Provided on request
Model | M1-125 | M1-250 | M1-400 | M1-630 | M1-800 | M1-1250 | M1-1600 | |
Rated Current ln (A) | 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 | 100, 125, 140, 160, 180, 200, 225, 250 | 250, 315, 350, 400 | 400, 500, 630 | 630, 700, 800 | 800, 1000, 1250 | 1250, 1400, 1600 | |
Rated Operating Voltage Ue (V) DC | 1P 250V 2P 500V 3P 750V 4P DC1000V | |||||||
Rated Insulation Voltage Ui (V) | 1000V | 1000V | 1500V | 1500V | 1500V | 1500V | 1500V | |
Uimp (kV) | 8kV | |||||||
Breaking Capacity (kA) Icu (1cs=75% Icu) | 250V | 35 | 50 | 50 | 50 | 65 | 65 | 65 |
500V | 25 | 35 | 35 | 35 | 50 | 50 | 50 | |
750V | 15 | 25 | 25 | 25 | 35 | 35 | 35 | |
1000V | 10 | 15 | 15 | 15 | 20 | 20 | 20 | |
Mechanical Life | Times | 7000 | 7000 | 4000 | 4000 | 2500 | 2000 | 2000 |
Breaking Times (ms) | 20 |