Features of CO2(R744) Heat Pump:
- The water can be heat up to 120ºC, high temperature output can reduce the volume of the storage tank and suitable for some specific usage (disinfection, cleaning)
- Suitable for low ambient. Even in -43ºC, it can efficiently offer heat
- Max COP is 5.5, our multi function model can reach max COP 7 (provide free cooling when producing heat)
- Inverter control to offer various power accordingly to real requirement, save energy
- Modules design, can reach higher Power by combined installation
- 6 layers of pressure protection
- Intelligent inverter control , can save 50% energy during defrosting
- Smart wireless control, also RS485/Modbus central control
- Programmable digital interface with touch keys
- Monobloc design, no need extra work for high pressure refrigerant connection
The advantages of CO2 as a refrigerant
- Climate-neutral environmentally friendly refrigerant R744 (CO2)
- Without environmentally hazardous decomposition products
- No additional contribution to the greenhouse effect (GWP = 1)
- Does not contribute to the ozone depletion (ODP = 0)
- No disposal and recycling requirements
- No availability constraints
- Low security requirements - Safety Group A1
- Non-toxic, non-flammable, thermally stable, compatible with other materials
Bitmap
| LYDS | 40ZF | 75ZF | 120ZF | 160ZF | 250ZF | |||
Low temperature condition | Heating Capacity | kW | 31 | 51 | 78 | 130 | 205 | ||
Power Consumption | KW | 9.2 | 14.9 | 23 | 38 | 61 | |||
COP | W/W | 3.36 | 3.42 | 3.39 | 3.42 | 3.36 | |||
Air Flow | m³/h | 3100 | 5120 | 7750 | 12900 | 20300 | |||
Cooling Capacity | kW | 21.8 | 36.1 | 55 | 92 | 144 | |||
EER | W/W | 2.36 | 2.42 | 2.39 | 2.42 | 2.36 | |||
Cool water flow | m³/h | 3.8 | 6.2 | 9.5 | 16 | 25 | |||
High temperature condition | Heating Capacity | kW | 25 | 42 | 61 | 110 | 155 | ||
Power Consumption | KW | 11.2 | 20 | 28 | 46 | 69 | |||
COP | W/W | 2.23 | 2.1 | 2.17 | 2.39 | 2.24 | |||
Air Flow | m³/h | 830 | 1060 | 2020 | 3650 | 5120 | |||
Cooling Capacity | kW | 13.8 | 21 | 33 | 64 | 86 | |||
EER | W/W | 1.23 | 1.04 | 1.17 | 1.39 | 1.24 | |||
Cool water flow | m³/h | 2.4 | 3.6 | 5.7 | 11 | 14.8 | |||
Power supply | V/Ph/Hz | 3phase 380V/50Hz/60Hz | |||||||
Heating type | Instant | ||||||||
Output Air temperature | ºC | 60~120 | |||||||
Input Air temperature | 0~80 | ||||||||
Water source inlet temperature | ºC | 5~30ºC | |||||||
Water source outlet temperature | ºC | 7~35ºC | |||||||
Compressor | Type | Semi-Piston | |||||||
Circulation water pump | Brand | Wilo | |||||||
Hot Air Pressure | Pa | 160 | |||||||
Hot Air Blower | Type | EC Fan | |||||||
Hot Air Heat exchanger | Type | Copper and Aluminum Coil | |||||||
Water Source connection | mm | DN32 | DN40 | DN50 | DN65 | DN80 | |||
Water Source Heat exchanger | Type | SST316L PHE | |||||||
Refrigerant | R744/ KG | 7 | 10 | 15 | 22 | 30 | |||
Controller | Brand | Carel | |||||||
Dimensions | Length | mm | 1200 | 1200 | 1600 | 2000 | 2500 | ||
Width | mm | 900 | 1200 | 1200 | 1200 | 1200 | |||
Height | mm | 1886 | 1886 | 1886 | 1886 | 1886 | |||
Unit noise level | dB(A) | 60 | 65 | 70 | 72 | 75 | |||
Net weight | kg | 650 | 800 | 1200 | 1800 | 2100 | |||
Inverter | VFD control | ||||||||
Note: | |||||||||
1.Working condition: | |||||||||
Low temperature condition: hot air inlet 30ºC,outlet 60ºC, water source inlet 12ºC outlet 7ºC | |||||||||
High temperature condition: hot air inlet 30ºC,outlet 120ºC, water source inlet 12ºC outlet 7ºC |