Tech Data |
Test Item | Technical Requirements (10KV) | Technical Requirements (35KV) | Test Result |
AC withstand voltage test | 39KV, 5min, No breakdown | 117KV, 5min, No breakdown | Pass |
Partial discharge test at room temperature | 15KV,<10pC | 45KV,<10pC | Pass |
Impulse voltage test | 95ºC~100ºC, ±95KV, 10 times each without breakdown | 95ºC~100ºC, ±200KV, 10 times each without breakdown | Pass |
Constant pressure load cycle test in air | 22KV, 95ºC~100ºC, heating for 5h per cycle, cooling for 3h. No breakdown for a total of 30 cycles | 65KV, 95ºC~100ºC, heating for 5h per cycle, cooling for 3h. No breakdown for a total of 30 cycles | Pass |
Constant pressure load cyclic test in water | 22kV, 95ºC~100ºC, heating for 5h per cycle, cooling for 3h. No breakdown for a total of 30 cycles | 65KV, 95ºC~100ºC, heating for 5h per cycle, cooling for 3h. No breakdown for a total of 30 cycles | Pass |