I. General information
AC hi-pot testing is the effective and direct way to test insulation strength for electrical equipments, apparatus or machines. It checks dangerous flaws which assure electrical equipment continuous working.
Typical applications include testing of transformers, switchgear, cables, capacitors, aerial motors platforms, hot sticks bucket bricks, vacuum bottles and other related equipment like vacuum interrupters, blankets, ropes, gloves, hydraulics hose, instruments transformers generators.
II. Features
Digital display panel mounted controls & indicators with easy to read legend.
Monitoring high voltage side voltage,low voltage side current and indicator of zero, power, working start,timing.
Over-current protection, zero-starting protection, sound and light alarm.
Continuously variable output from zero to full voltage.
Adjustable over current protection,with trip levels variable from 10 to 110%.
With new type time relay, time range is more wider (1S ~ 99H).
Using the latest current relay, more accurate and reliable.
Light weight, small size, easy to move.
III. Specifications
Input | AC220V ± 10% |
Frequency | 50Hz ± 1 |
Output | 0-100kV, AC RMS |
Rating | 100%Rated-1minute, 50%-continuous |
Capacity | 10kVA (based on selectable) |
HV Source | Epoxy resin cast HT transformer(Dry type testing transformer) |
Output control | Manual control |
Voltage accuracy | ≤ 1.0% (F.S) |
Current Accuracy | ≤ 1.0% (F.S) |
Timing range | 0-99H |
Metering | Digital display, kV meter: AC 0-100kV, mA meter: AC 0-100mA |
Humidity | 85% RH |
Environmental temperature | -20ºC~50ºC |
Weight | Control Unit:About 40kg Dry Type Testing transformer:About 75kg. |