Cold shrink joint body is made of liquid silicone rubber with hydrophobic performance and is erosion resistant. High elasticity and ability to shrink ensure powerful and constant active pressure between rubber and cable that can respond to expanding or shrinking cable diameters under load cycle.
This product has excellent insulating performance and high elastic, resistance and corrosion resistance of the electric mark etc, at the same time, excellent electrical performance; Long service life, after installation to always maintain the appropriate cable ontology radial stress. Make the interface bond within close, at the same time and cable keep share, won't because of the operation of breathing cable and electrical break-down; Stress cone and the composite insulation for an organic whole. Effective to solve the cable semi-conducting layer in the fracture of the stress concentration problems, ensure insulation, reliable, and safety of operation.

Lug 2. Marking tube 3. Cable insulation 4. Cold shrinkable termination 5. Stress cone 6. Insulation screen layer 7. Copper screen 8. Cold shrinkable protective tube 9. Three fingered tube 10. Copper braid wire | ||||
Size mm | 8.7/15kV | 12/20kV | 18/30kV | 26/35kV |
L | 252 | 370 | 370 | 450 |
A | ≥800 | ≥950 | ≥950 | ≥1300 |
Voltage Section number | 1 | 2 | 3 | 4 |
8.7/15 | 25-50 | 70-120 | 150-240 | 300-400 |
12/20,18/30,26/35 | 50-95 | 120-185 | 240-400 | 500-630 |
Lug 2. Marking tube 3. Cable insulation 4. Cold shrinkable termination 5. Stress cone 6. Insulation screen layer 7. Copper screen 8. Cold shrinkable protective tube 9. Three fingered tube 10. Copper braid wire 11. Cable | ||||
Size mm | 8.7/15kV | 12/20kV | 18/30kV | 26/35kV |
L | 180 | 288 | 288 | 370 |
A | ≥700 | ≥850 | ≥850 | ≥1200 |
Voltage Section number | 1 | 2 | 3 | 4 |
8.7/15 | 25-50 | 70-120 | 150-240 | 300-400 |
12/20,18/30,26/35 | 50-95 | 120-185 | 240-400 | 500-630 |


| ||||
Size mm | 8.7/15kV | 12/20kV | 18/30kV | 26/35kV |
L | 378 | 430 | 430 | 488 |
A | 1300 | 1600 | 1600 | 1800 |
Voltage Section number | 1 | 2 | 3 | 4 |
8.7/15 | 25-50 | 70-120 | 150-240 | 300-400 |
12/20,18/30,26/35 | 50-95 | 120-185 | 240-400 | 500-630 |
6~35KV cold shrinkable indoor, outdoor termination, and joint electrical performance
Rated voltage UO/U (Um) kV | 6/10(12.5) | 8.7/15(17.5) | 26/35(40.5) | Railway Uo=27.5 | Test result |
5min frequency voltage test | no flashover, without breakdown under 4.5Uo | no flashover, without breakdown | |||
1min frequency voltage under rain test | no flashover, without breakdown under 4Uo | no flashover, without breakdown | |||
Partial discharge at room temperature test | discharge volume under 1.73Uo ≤10PC | ≤1.6pC | |||
Constant voltage load cycle in the air test | heated 2.5Uo and conductor to a temperature to 95-100°C three times, no flashover, without breakdown | no flashover, without breakdown | |||
Partial discharge at high temperature test | heated cable conductor to 95-100°C, discharge volume under 1.73Uo ≤10PC | ≤1.6pC | |||
Partial discharge at room temperature test | discharge volume under 1.73Uo ≤10PC | ≤1.6pC | |||
Impulse voltage at high temperature test | 75kV | 95kV | 200kV | 25kV | no flashover, without breakdown |
heated cable conductor to 95-100°C,both positive and negative polarity 10 times, no flashover, without breakdown | |||||
Constant voltage load cycle test | heated 2.5Uo and conductor to a temperature to 95-100°C sixty times, no flashover, without breakdown | no flashover, without breakdown | |||
Partial discharge at high temperature test | heated cable conductor to 95-100°C, discharge volume under 1.73Uo ≤10PC | ≤1.6pC | |||
Partial discharge at room temperature test | discharge volume under 1.73Uo ≤10PC | ≤1.6pC | |||
Impulse voltage test | 75kV | 95kV | 200kV | 250kV | no flashover, without breakdown |
both positive and negative polarity 10 times, no flashover, without breakdown | |||||
15min frequency voltage test | no flashover, without breakdown under 2.5Uo | no flashover, without breakdown | |||
Outdoor termination salt spray test | 1.25Uo,1000h, no flashover, without breakdown, no significant electrical corrosion and mechanical damage | no flashover, without breakdown | |||
Indoor termination wet test | 1.25Uo, 300h, no flashover, without breakdown, no significant electrical corrosion and mechanical damage | no flashover, without breakdown |
Characteristics
Name: | Cold Shrinkable Cable Accessories |
Material: | PE |
Shrink ratio: | 2:1 |
Rated voltage: | 1kv-35kv |
Tensile strength: | ≥10.5Mpa |
Color: | Grey, red, yellow, green |
----After-sales service:
Provide free repair or replacement service for faults caused by product quality problems during the product warranty period.
Provide lifelong technical support and after-sales service to ensure that customers have no worries.


Our products cover electrical products such as transformers, ring main units, combiner boxes, inverters, and PCS. These products are widely used in the power system, industrial and mining enterprises, new energy, and other fields. We also have a sufficient inventory of spare parts and components to ensure that customers can receive prompt supplies when needed.
We have a professional technical team with deep knowledge and practical experience in the power industry, who can provide professional technical consultation and after-sales service to customers. Our service team always takes customer needs as the guide, actively responds to customer needs, and ensures customer satisfaction.


Packing | Plywood frame/container |
Shipping | By sea/air/train |

1. Who we are?
2.How can we guarantee quality?
3.What can you buy from us?
4.Why should you buy from us?
5.What services can we provide?