(Three-phase and three components)
TECHNICAL DATA
The products accord with the standards of GB17201-2006 and some special demands
Rated frequency 50HZ/60HZ
Ambient temperature -15ºC - +55ºC
Altitude not more than 4500M
Voltage Transformer
Rated voltage ratio(V) | Accuracy classes | rated output(VA) | Rated insulation level(KV) |
6000:√3/100:√3/100:3 | 0.2 0.5 | 30 | 7.2/32/60 |
10000:√3/100:√3/100:3 | 40 60 | 40.5/95/185 | |
11000:√3/110:√3/110:3 |
Current Transformer
Rated voltage ratio(V) | Accuracy classes | rated output(VA) | Rated short-time thermal current(I th) | Rated dynamic current(I dyn) | Rated insulation level(KV) |
5~300/5 | 0.2s 0.2 0.5 | 15 15 20 | 60I In | 150I In | 12/42/75 |
1. Rated output and its relative accuracy class only one altemative.
2.If user's data go beyond the above mentioned scopes, they may be subject to an agreement between manufacturer and purchaser.