1. GENERATOR DATA
Voltage Available:
50Hz: 380-400-415V/220-230-240V;
60Hz: 220-380-416-440-480V/110-208-220-240V
Any special voltage is also available as client's request
Prime Power:
Comply with GB/T2820-97(eqv.ISO8528).
Genset can run unlimitedly under certain power range.
One hour 10% over load in every 12 running hours is allowed;
Standby Power:
standby power is the limit value of maximum output for emergency use.
It is off-oil power,overloading is prohibited
2. MAIN SPECIFICATION
| Model | Continuous output (kw/kva) | Standby output (kw/kva) | Engine model | Alternator model |
| KPP1790-D | 1250/1560 | 1430/1790 | 4012-46TAG3A | STF-734D |
| Genset Data | Size & Weight (Silent type) | 7000*2300*2650mm (14600kgs) | ||
| Frequency | 50Hz (1500rpm) | |||
| Standard Features | Radiator 50OC max,fans are driven by belt, with safety guard/Ripple flex exhaust pipe, exhaust siphone, flange, muffler | |||
| Voltage | 400/230V | |||
| Phase & wires | 3phase, 4wires | |||
| Power factor | COSΦ=0.8 (lagging) | |||
| Battery | 24V | |||
| Fuel Tank | Included | |||
| Breaker | CHINT | |||
| Engine Data | Brand & Model | Perkins 4012-46TAG3A | ||
| Cycle | 4 stroke | |||
| Engine power (kwm) | 1643 | |||
| Air intake way | Turbo | |||
| Governor | Electronic | |||
| Cylinder | 12 | |||
| Bore*Stroke (mm) | 160*190 | |||
| Displacement (L) | 45.842 | |||
| Diesel consumption | 68.6g/kw.h against prime power | |||
| Natural gas consumption | 0.21m3/kw.h against prime power | |||
| Compression Ratio | 13.6:1 | |||
| Combustion system | Direct injection | |||
| Frequency & Speed | 50Hz, 1500RPM | |||
| Cooling way | Water cooled | |||
| Alternator Data | Brand & Model | KP-Stamford STF-734D | ||
| Alternator Power | 1320KW | |||
| Frequency & Speed | 50Hz, 1500RPM | |||
| phase & Voltage | 3 phases 4 wires & 400/230V | |||
| System | Brushless AC Synchronous, Single bearing | |||
| Insulation & Protection | H, IP44 | |||
| Voltage Regulator | Standard AVR | |||
| Control System | Brand & Model | Smartgen 7220 | ||
| Two language interface: Chinese/English | ||||
| Start or Stop Generator set manually / automatically; Open controller output can be defined as Pre-heat/Idle output. | ||||
| High Coolant temperature protection; Low Oil pressure protection. Over speed protection | ||||
| Over load protection; Generator over/under frequency protection: Generator over/under/unbalance voltage protection | ||||
3. PRODUCT FEATURES
(1).Full control panel with power indicator light and oil light.
(2).Emergency shutdown for low oil pressure and high water temperature.
(3).Large fuel tank ensure continuous running.
(4).Low noise & vibration.
(5).Compact structure.
(6).Reliable performance.
(7).Easy for installation and maintenance.
(8).50Hz and 60Hz both are available for choice












Audited Supplier