ADW series rail type multi-loop power meters are mainly used for measuring the full electric parameters of multiple three-phase circuits, up to four three-phase loop current inputs can be connected simultaneously. It can measure voltage and current, power, power factor, phase angle, unbalance, harmonic and other parameters.
![]() | ![]() |
ADW220 | ADW220 with Split-core CT |
RJ12 Interface design, super convenient to install


MK | MTL | AWT100 |
Digital Input: 12 Channels DI Digital Output: 4 Channels DO | Temperature: 12 External NTC Temp. Measurement; -20ºC~+100ºC; Accuracy ± 2ºC Residual Current: 4 Channels Residual Current Measurement; 10~3000 mA; Accuracy 1% (Class 1) | Downlink: RS485; Uplink: WiFi, 4G, 2G, NB, Lora, LoraWAN, Ethernet, GPS, Profibus |



just feel free to contact me to Create an IoT EMS Cloud Platform experienced account for you
Function | Description | |||
Energy Measurement | kWh (positive and negative) | |||
kvarh (positive and negative) | ||||
A, B, C three-phase positive kWh | ||||
Electric Parameter | U, I, P, Q, S, PF, Hz | |||
Harmonic | 2-31st voltage and current harmonic | |||
Communication | RS485 (MODBUS-RTU); baud rate 1200~38400 | |||
Key Programming | 4 keypads to set communication and parameters | |||
Display | LCD display, 8 digits | |||
LED Alarm | Over-voltage, over-current, interruption phase | |||
Data Log | Maximum demanded kWh and the time it happened. | |||
SOE | up to 200 pcs, record on-off status of DO/DI | |||
Pulse Output | Active optocoupler pulse output with open collector | |||
Multi-rate/Tariff | 4 time zones & 12 time periods |
Parameters | Description | |||
Input | Voltage | AC 3×220V/380V | ||
Overload: 1.2 times of rated value (continuous); 2 times of rated value / 1s | ||||
Power consumption:≤ 0.5VA | ||||
Current | AC 5A,100A,400A,600A;(external open-type CT) | |||
Overload: 1.2 times of rated value (continuous); 10 times of rated value / 1s | ||||
Power consumption:≤ 0.5VA | ||||
Frequency | 45~65Hz | |||
Measuring Accuracy | Voltage&Current | Class 0.5 | ||
Active Power | Class 1 | |||
Reactive Power | Class 2 | |||
Frequency | 0.05Hz | |||
2~31st harmonic | ± 1% | |||
Auxiliary Power | AC/DC 85~265V;consumption≤10VA; | |||
EMC | Better than grade 3 | |||
Safety | Withstand Voltage | >AC 2000V/1min | ||
Insulation Resistance | >100MΩ | |||
Environment | Working Temperature | -20ºC~+60ºC | ||
Storage Temperature | -40ºC~+70ºC | |||
Humidity | ≤95% (No condensation) | |||
Altitude | ≤2500m |
Specification | Input Current | Output Current | Hole Size (mm) for Conductor | Accuracy Class |
D10 | 5A | 1.25mA | 10mm | Class 0.5 |
D16 | 100A | 20mA | 16mm | |
D24 | 400A | 100mA | 24mm | |
D36 | 600A | 100mA | 36mm |