The Specification of Ore Box- RUISU-1200 Mining Enclosure
| Model | Ore Box- RUISU-1200 Mining Enclosure | |
| Dimensions | Enclosure Length x Width x Height | 38.1 ft x 7.2 ft x 7.5 ft |
| Number of installed mining rigs | 336 units with 3.25kW up to 4.0kW power consumption per rig | |
| Enclosure rating | NEMA 3 / IP54 | |
| Power Power | Power Input KW | Upper Limit: 1,354 KW |
| Input Voltage | 415VAC 3ph | |
| Inside Access | 3 phase power connection to inside access 4 Main Breakers | |
| Connection type | 3 Hot wires, 1 Neutral, 1 Ground, each phase Volts: 415VAC / 240VAC | |
| Distribution Panel and Breakers | Each cabinet has 4 power distribution panel. Each distribution panel: 1 x 600A 3-pole molded case main circuit breaker, 4 x 175A 3-pole molded case circuit breaker, 84 x 20A 1P circuit breaker, 6x6A 3P circuit breaker, 1x10A 2P circuit breaker, 3x20A 2P circuit breaker, 1x32A 4P circuit breaker, 1xSPD 40 (3L+N) surge protector | |
| Power Distribution & Cabling | 1. Power distribution unit: main panel circuit breaker (Schnei der), distribution circuit breaker (Nader), contactor (Nader).
| |
| Cooling | Cooling technology | Air Economizer with Evaporative cooling, 8 Panels per Container |
| Industrial grade Exhaust Fans (550W per fan) | 16 Fans with automated louvers | |
| Airflflow (Cubic-Feet-per-Minute) | 376,000 CFM (638,828 Cubic Meter/Hour) | |
| Air filtering system | Include air filter net and dust filter net | |
| Additional technical details | Security | Key locks standard to dual entry/egress security doors |
| Regulatory compliance | UL 489, Compliant to IEC 60950 and international wiring regulations | |
| External Environmental Operation limits | Operating temperatures | 40°F to 115°F |
| Operating humidity range | 0 to 90% RH (below Condensation point) | |
| Operating altitude | 0 to 5,000 ft | |













Audited Supplier