No. | Description | Technical parameters | |||
1 | Rated voltage, kV | 72.5 | 126 | 145 | 252 |
3 | Rated frequency, Hz | 50/60 | |||
4 | Rated current, A | 1600~4000 | 3150~4000 | ||
1min Power frequency withstand voltage | 140 | 230 | 265 | 460 | |
Lightning impulse withstand voltage | 325 | 550 | 650 | 1050 | |
5 | Rated short-circuit breaking current, kA | 25~40 | 40~63 | ||
7 | Rated short circuit breaking current (peak), kA | 63~ 100 | 100~ 157.5 | ||
8 | Rated short duration, s | 3 | 3 | 3 | 3 |
Rated out-of-phase breaking current | 10 | 10 | 10 | 10 | |
Rated cable(line) charging breaking current | 10 | 31.5 | 50 | 125 | |
Rated gas pressure, Mpa | 0.4 | 0.5 | 0.5 | 0.6 | |
Operation sequence | O-0.3s-CO- 180s-CO | ||||
SF6 gas leakage rate (per year) | ≤1% | ||||
14 | First of several genes | 1.5 | 1.55 | 1.5 | 1.3 |
Main loop resistance, μΩ | ≤40 | ≤45 | ≤45 | ≤50 | |
Heater voltage | AC220 | ||||
Control circuit and signal circuit voltage | DC220, DC230 | ||||
Motor voltage | DC220, DC230 |
Description
Outdoor Sulfur Hexafluoride (SF6) dead tank circuit breakers,
- Rated voltage : 69 KV
- Rated Continuous current : 1200 A / 1250A/1600A /2000A
- Interrupting current rating: 31.5 KA
- Frequency : 50 /60 Hz
- Basic insulation level (BIL): 350 KV
- With 6 pcs 150:5 ratio relaying accuracy bushing current transformers (CT)
- Outdoor usage, with 3 pcs SF6 interrupters
- 6-terminal pads with 4-hole each
- Trip-free spring operation mechanism
- 12-stages auxiliary contacts
- Anti-condensation cabinet heater
- Control wiring and terminal blocks
- 110VDC trip coil
- 48 VDC /110VDC closing coil
- 110 /220 VDC Auxiliary voltage
- with operation handle
- with isolating switches
- mechanical position indicator
- CB frame grounding terminal holes
- hot-dipped galvanized mounting structure
- with gas charging device with regulator valve
- with gas leak detector
- with spare SF6 gas
Circuit breakers meet the requirements specified in EN 62271-1, EN 62271-100, EN 60273, and other relevant EN (IEC) standards.

220KV 3Ph Live Tank SF6 Gas Circuit Breaker
Service environment
2. Daily average ambient air relative humidity ≤ 95%, on average ≤ 90%;
3. Wind pressure: less than 700pa.
4.Altitude: less than 3000m.
5.Earthquake intensity: not more than 9 degrees.