It has a wide range of applications, especially suitable for use in places with high fire protection requirements, such as mines, oil fields, subways, power plants, schools, hospitals, commercial centers, high-rise buildings and all indoor configuration systems.
This product conforms to the national standard GB1094.1-2013(IEC 60076) power transformer and GB / T6451-2015 indoor dry-type transformer technical parameters and requirements. Epoxy resin pouring transformer is a solid insulation encapsulated winding power transformer. Epoxy resin dry-type transformer uses epoxy resin as insulation material. High and low voltage winding is made of copper strip (foil), epoxy resin is poured and solidified in vacuum to form high strength FRP body. Insulation grade is F and H. Epoxy resin dry-type transformer has the characteristics of good electrical performance, strong lightning shock resistance, strong short-circuit resistance, small size and light weight etc.. The temperature display controller can be installed to display and control the operating temperature of the transformer winding to ensure the normal service life of the transformer.



Transformer TypeTransformer | Resin Cast Dry Type |
Model | SCB10-50/10 |
Number of Phase | Three Phase |
Winding Type | Two Winding |
Winding Material | Aluminum/Copper |
Rated Capacity | 50kVA |
High Voltage | 10/11kV |
Low Voltage | 0.4kV |
Tapping Ran | ±2x2.5% |
Impedance Voltage | 4% |
Load Loss (120°C) | 1kW |
No-load Loss | 0.27kW |
No-load Current | 2% |
Frequency | 50/60Hz |
Connection Group | Yyn0/Dyn11 |
Cooling Method | ANAF |
Insulation Class | F |
Thermal Class | F1 |
Operation Altitude | ≤1000m≤ 1000 m |


The company has strong technical force, advanced equipment at home and abroad, innovative ideas, rich manufacturing experience, and a complete range of products. The company has passed ISO9001 international quality management system certification, CCC certification, and won the national high-techenterprises and other honours..












Quotation and Ordering Required Information:
Transformer Type:
Rated Capacity: kVA
Phase: ( )Three Phase ( )Single Phase
Frequency: ( )50Hz ( )60Hz
Rated Voltage (HV/LV): kV / kV
Tapping Range: ± x %
Insulation Level: LI AC / LI AC
Vector Group: ( )Dyn11 ( )Yyn0 ( )Other
Short-circuit impedance: Uk= %
Service conditions: Altitude: m
Ambient temperature: ºC
Cooling Method: ( )ONAN ( )ONAF
Oil labeling:
Quantities ordered and time of delivery:
Other requires:
(If you have, It will be better send us technical specification/date documents.)