Type | Designation | Nominal thickness mm(±0 . 02) | Scope of application Class A or B | |
T-FMTNHJ-1 | Single-side PE film enhanced phlogopite mica tape | 0.12 | B,A | |
T-FMTNHJ-2 | Double sides PE film enhanced phlogopite mica tape | 0.14 | B,A | |
T-FMTNHJ | Single-side fiberglass Enhanced phlogopite mica tape | 0.12 | B,A | |
T-FMTNHJ-3 | Fiberglass and PE film enhanced phlogopite mica tape | 0.14 | B,A | |
T-FMTNHJ-S | Double sides fiberglass enhanced phlogopite mica tape | 0.14 | B,A | |
T-FMTNHD | Single-side fiberglass enhanced calcined mica tape | 0.12 | B,A | |
T-FMTNHD-3 | Fiberglass and PE fim enhanced calcined mica tape | 0.14 | B,A | |
T-FMTNHD-S | Double sides fiberglass enhanced calcined mica tape | 0.14 | B,A | |
T-FMTNHH-1 | Single-side PE film enhanced synthetic mica tape | 0.12 | A | |
T-FMTNHH-2 | Double sides PE film enhanced synthetic mica tape | 0.14 | A | |
T-FMTNHH | Single-side fiberglass enhanced synthetic mica tape | 0.12 | A | |
T-FMTNHH-3 | Fiberglass and PE film enhanced synthetic mica tape | 0.14 | A | |
T-FMTNHH-S | Double sides fiberglass enhanced synthetic mica tape | 0.14 | A | |
N o | I t em | V a l u e | |||||
mica content % | ≥55 | ||||||
2 | organic silica-gel content % | ≤17 | |||||
3 | volatile content % | ≤1.0 | |||||
4 | tensile strength N/cm | ≥80 | |||||
5 | volume resistance Ω ·m | ≥1.0×10^10 | |||||
6 | dielectric strength MV/m | ≥10 | |||||
7 | insulation resistance | MΩ | phlogopite mica tape calcined mica tape | ≥1.0 | |||
synthetic mica tape | ≥0.4 | ||||||
8 | fire-resistan performance | phlogopite mica tape calcined mica tape | Class B(750-800ºC),90min voltage test 1KV | ||||
synthetic mica tape | Class A(950-1000ºC),90min voltage test 1KV |
a. The fire-resistance cable that wrapped with the mica tape produced could easily pass the burning test of GB19216-2003/IEC 60331-21:1999<Tests for electric or optical fibre cables under fire conditions>.
b. It is the best quality fire proof and fire-resistant material.
c. Cable with the synthetic mica tape single layer wrapping can continue the normal circuit operating with 3 hours at 1000ºC.
d. Cable with the fire-resistant mica tape will not get fire because of the short circuit resulting from the heat of over load of the cable in 3 hours.
e. Cable with fire-resistant mica tape will reduce and prevent from producing and releasing poisonous smoke and gas when burning.
f. It has good fire,acid,alkali,corona and irradiation-resistant characteristic.
g. It has completely non-flammable and heat-resistant performance.
It should be stored in the dry and clean warehouse and the shelf life is 6 months after the manufacturing date.