Type | Thrust Output (Nm) | Travel (mm) | Full travel time (S) | |
Type III(4-20mA) | Type III(0-10mA) | |||
DKJ-4100M DKJ-4200M DKJ-4300M | DKJ-410M DKJ-420M DKJ-430M | 4000 | 10 16 25 | 8 12.8 20 |
DKJ-5400M DKJ-5500M | DKJ-540M DKJ-550M | 6400 | 40 60 | 32 48 |
DKJ-6600M | DKJ-660M | 16000 | 100 | 80 |
III. Main Technical Parameters
1. Input signal: Type II 0-10mA DC; Type III 4-20mA DC
2. Input channel: 3
3. Input channel impedance: Type II 200Ω; Type II 250Ω
4. Output torque: See table above
5. Full travel time: See table above
6. Limit of basic error:±2.5%
7. Dead zone:<=3%
8. Damping characteristic: <=3 half cycles
9. Return difference: ±1.5%
10. Power supply voltage: 220V (±10%,±15%) at frequency 50Hz
11. Service environment temperature: Actuator:-10~+55°C or -25~+70°C; Amplifier:0~+50°C
12. Relative humidity of service environment: Actuator:<=95%; Amplifier: 10%-70%
IV. Overall Dimensions
Type | A×B×C (mm) | D | E | F | I | H | G | Nominal diameter of valve (DN) | |
Type III(4-20mA) | Type III(0-10mA) | ||||||||
DKZ-4100M DKZ-4200M DKZ-4300M | DKZ-410M DKZ-420M DKZ-430M | 230×500×520 | 2-Φ10.5 | Φ80 | M8 | Φ60H8 | 72 | 150 | 15,20,40,50 |
DKZ-5400M DKZ-5500M | DKZ-540M DKZ-550M | 230×500×564 230×500×594 | 4-Φ10.5 4-Φ10.5 | Φ105 Φ118 | M12×1.25 M16×1.5 | Φ80H8 Φ95H8 | 105 112 | 150 | 60,80,100,125,150,200 |
DKZ-6600M | DKZ-660M | 230×615×670 | 4-Φ16 | Φ170 | M20×1.5 M20×1.5 | Φ100H8 | 92 | 200 | 250,300 |
V. Terminal Wiring Diagram
2.1 DKZ (ZKZ)-D Type Electronic Linear Electric Actuator
Type | Thrust Output (Nm) | Travel (mm) | Full travel time (S) |
DKZ-4100D | 4000 | 10 | 8 |
DKZ-4200D | 16 | 12.8 | |
DKZ-4300D | 25 | 20 | |
DKZ-5400D | 6400 | 40 | 32 |
DKZ-5500D | 60 | 48 | |
DKZ-6600D | 16000 | 100 | 80 |
III. Main Technical Parameters
1. Input signal: Type II 0-10mA DC; Type III 4-20mA DC
2. Feedback signal: Type II 0-10mA DC; Type III 4-20mA DC
3. Input channel impedance: Type II 250Ω; Type II 200Ω
4. Thrust output, full travel time: See table
5. Basic error: ±1.5%
6. Return difference: ±1.5% (±1%)
7. Dead zone: 0.5-5% adjustable
8. Field manual operation function
9. Range of electric limit: Lower limit0-90%; upper limit 10-100%
10. Optional breaking-off signal protection states: a. Stop in situ b. Auto off C. Auto fully-open
11. Fault alarm: Two ways of alarm output (over-torque alarm and breaking-off signal alarm), a pair of normally open contact points for each
12. Power supply voltage: 220V (±10%, ±15%) at frequency 50Hz
13. Service environment: Temperature: Actuator: -10~+70°C or -25~+90°C;Humidity: <=80% without corrosive substances in ambient air
14. Protection class: Ordinary IP55, outdoor IP65
IV. Overall and installation dimensions of DKZ-D type electronic integrated actuator
Type | Travel (mm) | A×B×C (mm) | D | Valve stem connection hole (E) | Flange inside diameter (K) | Flange connection (M) | Connecting hole (N) | Connecting nominal diameter (DN)(reference) |
DKZ-4100D | 10 | 230×500×520 | 72 | M8×1.25 | Φ60 D9 | Φ80 | 2-Φ10.5 | 15 20 25 32 40 50 |
DKZ-4200D | 16 | |||||||
DKZ-4300D | 25 | |||||||
DKZ-5400D | 40 | 230×500×564 | 105 | M12×1.25 | Φ80 D9 | Φ105 | 4-Φ10.5 | 65 80 100 |
DKZ-5500D | 60 | 230×500×594 | 112 | M16×1.5 | Φ95 D9 | Φ118 | 125 150 200 | |
DKZ-6600D | 100 | 230×615×670 | 95 | M20×1.5 | Φ100 D9 | Φ170 | 4-Φ16 | 250 300 |