Technical parameters of circuit breaker
| No. | item | unit | Data | note | |
| 1.1 | installation | indoor/outdoor | |||
| 1.2 | Ambient temperature | ºC | -40 ~ 60 | ||
| 1.3 | sun's radiation | W/cm2 | 1000 | ||
| 1.4 | humidity | % | average day :95% | ||
| 1.5 | The altitude | m | ≤2000 | ||
| 1.6 | The wind speed | m/s | 34 | ||
1.7 | earthquake conditions | Horizontal acceleration | g | General area 0.15, strong earthquake area 0.3 | |
| Vertical | 0.075,0.15 | ||||
| acceleration |
- rating parameters
| No. | name | unit | parameter | note |
| 2.1 | Rated voltage | kV | 126 | |
| 2.2 | Nominal voltage | KV | 126 | |
| 2.3 | Max.working voltage | kV | 126 | |
| 2.4 | Rated current | A | 3150 | |
2.5 | Rated short time withstand voltage (4S) | kA | 40 | |
2.6 | Rated withstand voltage (peak value) | kA | 100 | |
2.7 | Rated power frequency withstand voltage | kV | 230 | To earth |
| 230+70 | interrupter | |||
2.8 | Rated lightning impulse withstand voltage(peak) | kV | 550 | To earth |
| 550+100 | interrupter | |||
2.9 | SF6 rated pressure | MPa | 0.4 | |
| 0.35 | Alarm |
| pressure | ||||
0.30 | Lock pressure | |||
| 3.0 | SF6 In a flat rate | % | ≤0.5 |