It is possible to select and switch between two power sources according to requirements, ensuring uninterrupted operation of key power sources. When one power supply has overvoltage, undervoltage or phase loss, it will automatically switch to another power supply or start the generator.
Built-in RS485 communication interface, communication protocol MODBUS-RTU, realize real-time data upload, remote data configuration and status monitoring, as well as remote control, telemetry, remote control and remote adjustment functions.
Mainly used in hospitals, shopping malls, banks, hotels, high-rise buildings, fire protection and other places that do not allow long-term power outages with uninterrupted power supply required.
Selection
YCQ9Ms | 125 | M | 3 | 100A | 100A | ||
Product name | hell frame grade | Breaking capacity | Number of poles | Rated current | Controller code | ||
Automatic transfer switch | 63: (10-63A) | M: Standard type | 3:3P 4:4P | 16,25, 32,40, 50,63, 80,100, 125,140, 160,180, 200,225, 250,315, 400,500, 630,800, | Y: Integrated LED display (Standard default) W2: Split LED display W3: Split LED display | ||
125: (16-125A) | |||||||
250: (100-250A) | |||||||
400: (250-400A) | |||||||
630: (400-630A) | |||||||
800: (630-800A) |
Type | YCQ9Ms | |||||||||||
Shell frame | 63 | 125 | 250 | 400 | 630 | 800 | ||||||
Rated working current In(A) | 10, 16, 20, 25, 32, 40, 50, 63 | 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 | 100, 125, 140, 160, 180, 200, 225, 250 | 250, 315, 350, 400 | 400, 500, 630 | 630, 800 | ||||||
Number of poles | 3, 4 | |||||||||||
Electrical class | Class CB | |||||||||||
Use category | AC33iB | |||||||||||
Rated working voltage Ue(V) | AC380, 400 | |||||||||||
Rated insulation voltage Ui(V) | AC690 | AC800 | ||||||||||
Rated impulse withstand voltage Uimp(KV) | 8 | |||||||||||
Rated short-circuit breaking capacity Icn(KA) | 15 | 25 | 25 | 35 | 35 | 35 | ||||||
Electrical life | 1000 | 1000 | 500 | |||||||||
Mechanical life | 5000 | 3000 | 2500 | |||||||||
Rated working system | Uninterrupt working system | |||||||||||
Overvoltage transfer setpoint | 270VAC | |||||||||||
Undervoltage transfer setpoint | (70%~85%)Ue continuously adjustable | |||||||||||
Contact switch time | <4s | |||||||||||
Disconnection delay | 0.5s-30s continuously adjustable | |||||||||||
Shutdown delay | 0.5s-30s continuously adjustable |

Dimensions Specification | A | D | B | C | H1 | H2 | |||||||||||||||||
3P | 4P | 3P | 4P | ||||||||||||||||||||
YCQ9Ms-63 | 380 | 405 | 250 | 340 | 365 | 230 | <160 | 25 | |||||||||||||||
YCQ9Ms-125 | 405 | 435 | 250 | 365 | 395 | 230 | <170 | 25 | |||||||||||||||
YCQ9Ms-250 | 450 | 480 | 250 | 410 | 440 | 230 | <190 | 25 | |||||||||||||||
YCQ9Ms-400 | 570 | 620 | 330 | 510 | 560 | 300 | <200 | 25 | |||||||||||||||
YCQ9Ms-630 | 680 | 740 | 330 | 620 | 680 | 300 | <250 | 25 | |||||||||||||||
YCQ9Ms-800 | 750 | 820 | 330 | 690 | 760 | 300 | <250 | 25 |