Measurement Span/Range | MPa | psi (/D1) | bar (/D3) | kgf/cm2 (/D4) | |
A | Span | 10 to 200 kPa | 1.45 to 29 | 0.1 to 2 | 0.1 to 2 |
Range | −100 to 200 kPa | −14.5 to 29 | −1 to 2 | −1 to 2 | |
B | Span | 0.02 to 2 | 2.9 to 290 | 0.2 to 20 | 0.2 to 20 |
Range | −0.1 to 2 | −14.5 to 290 | −1 to 20 | −1 to 20 | |
C | Span | 0.1 to 10 | 14.5 to 1450 | 1 to 100 | 1 to 100 |
Range | −0.1 to 10 | −14.5 to 1450 | −1 to 100 | −1 to 100 | |
D | Span * | 0.5 to 50 | 72.5 to 7200 | 5 to 500 | 5 to 500 |
Range * | −0.1 to 50 | −14.5 to 7200 | −1 to 500 | −1 to 500 |
Model | SufxCodes | Description | |||||||||||
EJA510E EJA530E | . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . | Absolute pressure transmitter Gauge pressure transmitter | |||||||||||
Output signal | -D ............................. -J ............................. -F ............................. -G............................. -Q............................. | 4 to 20 mA DC Output with digital communication (BRAIN protocol) 4 to 20 mA DC Output with digital communication (HART 5/HART 7 protocol)*1 Digital communication (FOUNDATION Fieldbus protocol, refer to GS 01C31T02-01EN) Digital communication (PROFIBUS PA protocol, refer to GS 01C31T04-01EN) Low Power, 1 to 5 V DC with digital communication (HART 7 protocol) | |||||||||||
Measurement span (capsule) | A............................ B............................ C............................ D............................ | 10 to 200 kPa (1.45 to 29 psi) 0.02 to 2 MPa (2.9 to 290 psi) 0.1 to 10 MPa (14.5 to 1450 psi) 0.5 to 50 MPa (72.5 to 7200 psi)*10 | |||||||||||
Wetted parts material *2 | S......................... H......................... | Process connector 316L SST *11# Hastelloy C-276 *3# | Diaphragm Hastelloy C-276 *3# Hastelloy C-276 *3# | Others 316L SST # Hastelloy C-276 *3# | |||||||||
Process connections * For a diaphragm seal system, refer to process connections code table (p.6). | 4...................... 7...................... 8...................... 9...................... | 1/2 NPT female 1/2 NPT male G1/2 DIN 16 288 male *4 M20×1.5 DIN 16 288 male *4 | |||||||||||
─ | N.................... | Always N | |||||||||||
─ | -0 ................ | Always 0 | |||||||||||
Amplifer housing | 1............... 3............... 2............... | Cast aluminum alloy Cast aluminum alloy with corrosion resistance properties *5 ASTM CF-8M stainless steel *6 | |||||||||||
Electrical connection | 0............ 2............ 4............ 5............ 7............ 9............ A............ C............ D............ | G1/2 female, one electrical connection without blind plugs 1/2 NPT female, two electrical connections without blind plugs M20 female, two electrical connections without blind plugs G1/2 female, two electrical connections with a blind plug*7 1/2 NPT female, two electrical connections with a blind plug*7 M20 female, two electrical connections with a blind plug*7 G1/2 female, two electrical connections and a 316 SST blind plug 1/2 NPT female, two electrical connections and a 316 SST blind plug M20 female, two electrical connections and a 316 SST blind plug | |||||||||||
Integral indicator | D......... E......... N......... | Digital indicator *8 Digital indicator with the range setting switch (push button) *9 (None) | |||||||||||
Mounting bracket | L...... N...... | 316 SST 2-inch pipe mounting None | |||||||||||
Optional Codes | ¨/ Optional specifcation |


(hereinafter referred to as Hanshan Intelligent Technology Co., Ltd. group) was formally established in Shanghai in 2013;
Its founding team are all from top international automation companies; have over 20 years of experience in automation industry; over 20 years of experience in automation engineering; over 10 years of experience in consulting and implementation of digital solutions; aiming at providing quality automation and digitization products and services for global customers; the company's headquarter is located in Shanghai, China;
The company has been deeply cultivated in the petrochemical industry for more than 20 years; has in-depth understanding of the automation and digitalization needs of upstream, midstream, and downstream enterprises; provides professional products and solutions based on automation and digitalization and full life cycle services for petroleum, chemicals, electric power, biomedicine, APIs, food and beverage, liquor, metallurgy, and non-ferrous metals.



How do I select the right product?
A:Upon receipt of your inquiry, we will provide you with a comprehensive technical document. This will enable you to verify the detailed process parameters and technical specifications required. Based on your specific requirements, we will then recommend the most suitable model.
I would like a confirmed model. Can you provide that?
A:Certainly. Once you send us the model you require, we will first need to verify the suitability of the model. If necessary, we will provide some more cost-effective optimization suggestions. After confirmation, we can proceed with a formal quotation.
Measurement rang