We are professional manufacturer of current transformer ,voltage transformer, Vacuum Circuit Breakers/Recloser,Isolation switches,Dropout Fuse Cut-out,Lightning Arresters,High and Low Voltage Cabinets,Metering Devices,Power Distribution Transformers etc.

GENERAL
The intelligent circuit breaker meets the requirements of GB / T 1984-2014 high voltage AC circuit breaker, DL / T 402-2016 high voltage AC circuit breaker, and DL / T 403-2000 technical conditions for ordering 12kV ~ 40.5kV high voltage vacuum circuit breaker and DL / T 721-2013 remote terminal of the distribution automation system.
MODEL DESCRIPTION

USAGE: ENVIRONMENTAL CONDITION
- Altitude: ≤ 1000m, If the altitude is higher than 1000m, the rated insulation level shall be corrected accordingly.
- Ambient temperature: -40oC ~ +45oC,
- Maximum daily temperature difference: 25K
- Humidity: Average daily relative humidity: 95%, average monthly relative humidity: 90%.
- Sunshine intensity: not more than 0.1W/cm2
- Wind Speed: 34m/s
- Wind pressure: 700Pa
- Pollution level: e - level
- Icing thickness: Not more than 10mm
- Resistance to floor drain: horizontal acceleration 0.3g, vertical acceleration 0.2g
☆ Ceramic vacuum arc extinguishing chamber is adopted, with strong arc extinguishing ability and short-circuit breaking ability;
☆ It has the advantages of being explosion-proof, anti-condensation, anti-pollution, and no environmental impact
☆Air silicone rubber and engineering plastic composite insulation are adopted to avoid the possibility of insulation accidents caused by oil deterioration in oil insulation;
☆ The body can be equipped with an isolating switch to form a "combined electrical apparatus" with obvious fracture. The user can choose to use a silicone rubber insulating sheath on the isolating switch. The sheath has the advantages of rain, snow, sand, and strong resistance to pollution and corrosion, which can effectively improve the anti-freezing and anti-oxidation ability of the isolating switch;
☆ It can realize three-stage protection, zero sequence grounding protection, reclosing, and remote communication.
MAIN TECHNICAL PARAMETERS
No. | Item | Unit | Data | ||
1 | Rated frequency | Hz | 50 | ||
2 | Rated voltage | kV | 12 | ||
3 | Rated current | A | 630 / 1250 | ||
4 | Rated short-time power frequency withstand voltage | Interphase, to earth(wet) | kV/min | 34/1 | |
Interphase, to earth(dry) | 42/1 | ||||
Fracture (dry) | 48/1 | ||||
Secondary circuit to earth | 2/1 | ||||
5 | Rated lightning impulse withstand voltage | Interphase, to earth | kV | 75 | |
Fracture | 85 | ||||
6 | Rated short-time withstand current and duration | kA/s | 20/4 25/4 | ||
7 | Rated Short-circuit breaking current(Effective value) | kA | 20 / 25 | ||
8 | Rated short-circuit making current(peak) | 50 / 63 | |||
9 | Rated Peak-withstand current | 50 / 63 | |||
10 | Main circuit resistance | Without Isolation Switch | μΩ | not less than 120 | |
With Isolation Switch | not less than 200 | ||||
11 | Rated Short-circuit breaking current breaking times | Times | 30 | ||
12 | Rated operating voltage and Rated Voltage for auxiliary(control) circuit | V | AC/DC220 DC48, DC24 | ||
13 | Mechanical life | Times | 10000 | ||
Note: If the altitude is over 1000m, the rated insulation level should be modified as appropriate. |
OUTLINE AND INSTALLATION DIMENSION

All products have undergone professional testing and certification.


Our customers are located all over the world.