Model NO.:
AC400-1000KVA
Conditions of Use:
Trailer Type, Marine, Land Use
Usage:
Standby Unit, Common Units
Output Type:
AC Three Phase
Cooling Method:
Air Cooled
Installation Method:
Portable
Generator Type:
Diesel Generator
Voltage:
400V,415V,440V,480V
Power:
1000kVA
Power Factor:
1
Frequency:
50Hz, 60Hz
Min Step:
1kw
Control:
Local and Remote
Communication:
RS485
Resistor:
Metal Alloy
Warranty:
12 Months
Trademark:
Triumph Load
Transport Package:
Wooden Case
Specification:
ISO
Origin:
China
HS Code:
90303900
Product Description

1000kW Generator Testing Resistive Load Bank

Product Introduction

   The system can accurately test the output power and load capacity of various generator sets.The system consists of two parts of measurement and loading, including AC load bank, data acquisition system, automatic load and drop control system, cooling device, auxiliary control,PC software,and so on.The user can freely select local control or software control to operate the load bank.

Technical Parameters

Technical Parameters

Rating Voltage/Frequency

AC 415V/50Hz, 3 phase 4 wire

Max Load Power

Resistive Load: 1000kW

Load Step

Resistive Load:13 steps; 1,2,2,5,10,10,20,50,100,200,200,200,200kW

Power Factor

1

Load Tolerance(each step)

±5%

Load Tolerance(overall)

±3%

Display Precision

0.5 class

Control Power Supply

Input415VAC 3 phase 4 wire 50hz

Wire Connection

Load Power Supply Input--Copper bar (star connection)

Control power supply input--Connector bar

Communication Interface

RS485, RS232

Insulation Class

F

Working Mode

Continuous Working

Cooling

Forced air cooling,Horizontal inlet air,Horizontal outlet

Transportation

Hoisting, there are lifting lug in top of case and wheel castors in bottom

Dimension

Approximately; 2440 mm×1250mm×1800mm

(Width *Length *Height)

Operating Environment Parameter

Ambient Temperature

-10ºC~+50ºC 

Relative Humidity

≤95%

Altitude

≤2500 meters

Atmospheric Pressure

86~106kPa