Battery Capacity Tester Battery Discharger Electrical Laod Bank Stainless Steel Cabinet

Price Negotiable
Min Order 1 Set
Availability In Stock
Shipping From Sichuan, China
Popularity 423 people viewed
After-sales Service:
Yes
Warranty:
3 Years
Type:
Storage Battery Tester
Test Region:
Volume
Application:
Lead-acid Battery
Customized:
Customized
Name:
Battery Capacity Tester Battery Discharger
Voltage Resolution of Whole Set:
0.01V
Discharge Current Range:
5-200A
Discharge Battery Capacity:
50ah-2000ah
Control Accuracy of Discharge Current:
0.1A
Current Test Accuracy:
1%
Heat Disspation:
Forced Wind
Voltage Test Accuracy:
0.5%
Trademark:
Rata
Transport Package:
Wooden Case/Customized
Origin:
China
HS Code:
9030899090
Product Description
Battery Capacity Tester Battery Discharger


Battery Discharger Function and Application

1. Battery discharger is mainly used for the discharge test of backup power lead-acid battery in Telecom, mobile, Unicom and DC power industry.
2. It has three functions of battery fast capacity test, online monitoring and capacity check test.
3. It has high integration, small volume and perfect function.


Battery Discharger Specification
 
Note: all parameters are for reference only and can be customized
ModelType of cell voltage measurementConstant current discharge voltage rangeWorking voltage              (DC / AC optional)Weight
RATA-FDY481502V/6V/12V40~56VAC 220V ±15%Less than 10.5Kg
RATA-FDY483002V/6V/12V40~56VAC 220V ±15%Less than 13Kg
RATA-FDY486002V/6V/12V40~56VAC 220V ±15%Less than 15Kg
RATA-FDY220302V/6V/12V180~280VAC 220V ±15%Less than 10.5Kg
RATA-FDY220602V/6V/12V180~280VAC 220V ±15%Less than 13Kg
Note: all parameters are for reference only and can be customized
Voltage resolution of the whole set0.01V
Voltage test accuracy0.5%
Working range of discharge current5-200A
Discharge battery capacity range50AH~2000AH
Constant current discharge voltage rangeAccording to customer needs
Control accuracy of discharge current0.1A
Current measurement accuracy1%
Type of cell voltage measurement2V\12V
Measurement range of cell voltage0~15V
Cell voltage resolution2V:0.001V /12V:0.01V
Number of monosomic segments detected1~240
Working voltageAC 220V±15%
Cooling modeStrong wind cooling
Communication modeRS232 communication and SD card communication
Display mode7 inch color LCD display with touch

  • Similar Products