| | | INPUT | | AC voltage | | | ·Single phase | 1×230V(220,240) | | ·Three phase | 3×400V(380,415) | | Input voltage tolerance | ±10% | | Input Wiring | 3 Phase 3 Wirse or 3 Phase 4 Wires | | Input frequecny | 50Hz(60Hz) | | Input frequecny tolerance | ±5% | | Input Protection | Thermic Magnetic Overcurrent protection via MCCB |
| OPTIONS | | Rectifier | Other input voltage(1×110 to 3×690VAC) | | Harmonic filter for THDi≈15% | | Blocking diode | | Surge and Lightning protections | | Voltage ripple filter | | Bettery | Battery circuit protection box | | Battery reversed polarity detection | | Battery low-voltage disconnection contactor (LVD) | | Battery room temperature sensor | | Battery cabinet / rack | | Battery monitoring system | |
| System | Parallel configurations | | Dropping diodes/DC-DC converter | | Earth fault monitoring | | Internal cabinet lighting | | Anti-condensation heater | | Output breaker | | Front-panel analog meters/digtal meters | | DC distribution | | Temparature compensation | | AC high and AC low alarm/protection | | DC high and DC low alarm/protection | | AC fault alarm | | LED test function | | Mechanical | Other frame colour | | Up to IP55 external | | Plate thickness | | Specified cabinet identification (tag, nameplate) | | Communication | Modbus TCP/IP | | modbus RTU(RS485) | | DNP3.0 protocol | | Volt-free contacts | | Transducers 4-20mA | | Remote monitoring |
| | | OUTPUT | | Nominal DC voltage | 24/48/110/125/220/240/400 | | Output voltage range | 0-1.5×nominal voltage (adjustable) | | Nominal DC current | 10-1500A | | Output current range | 0-1.1×nominal current(adjustable) | | Voltage stability | ±1% in float mode, input within tolerance | | Voltage ripple | 1% RMS(with battery connected) | | Current Limitation | Battery current limitation can be adjusted | | Filtering | L-C Filter | | Output Protection | Short Circuit, NH Fuse and Overvoltage protection |
| BATTERY | | Type | Lead acid or nickel cadmium, vented or recombination and Lithium battery |
| COMMUNICATION | | Communication | RS232, Modbus RTU |
| GENERAL DATA | | Operating temperature | 0 to 50 °C | | Storage temperature | -20 to +70 °C | | Relative humidity | < 95 % non condensing | | Operating altitude | 1000 m max without derating | | Cooling | Fan cooling or Natural cooling according to rating | | Efficiency | 90% according to rating | | External protection | IP20 | Noise (at 1m in front of the unit) | 55 - 65 dB according to rating | | Cabinet color | RAL 7035 | | Dimensions | Varying according to ratings & options |
| STANDARDS | | IEC60146-1-1:2009 | Semiconductor converters - Specification of basic requirements | | IEC62040-1:2008+AMD1:2013 | Uninterruptible power systems (UPS) - Part 1-2: General and safety requirements for UPS in restricted access locations | | IEC62040-2:2006 | Uninterruptible power systems (UPS) - Part 2: Electromagnetic compatibility (EMC) requirements | | IEC61439-1:2011 | Low voltage switchgear and controlgear assemblies - Part 1: General rules | IEC60529:1989+ AMD1:1999 | Degrees of protection provided by enclosures (IP Code) | | IEC60076-11:2004 | Power transformers - Part 11: Dry type transformers |
| European Directives | Low voltage directive: 2006/95/EC and 2014/35/EU EMC directive: 2004/108/EC and 2014/30/EU CE Mark |
|