Small size,high accuracy,good consistency, for the precise measurement of current and power
Key words: current transformer
Structural parameters:

Front view Left View
The main technical parameters:
| Model | ZMCT102W |
| Rated input current | 5A |
| Rated output current | 2.5mA |
| turns ratio | 2000:1 |
| phase angle error | ≤30'(input 1A,sampling resistor 100Ω) |
| linear range | 0~20A(sampling resistor 100Ω) |
| linearity | ≤0.2%(5%dot~120%dot) |
| Permissible error | -0.2%≤f≤+0.2%(input 1A,sampling resistor 100Ω) |
| isolation voltage | 4500V |
| application | the precise measurement of current and power |
| Encapsulation | Epoxy |
| installation | Output leads installation (conventional lead length shown in drawing) |
| operating temperature | -40ºC~+85ºC |
Direction for use:
Figure I FigureII1. The typical usage of the product is for the active output ( FigureI) . R is a sampling resistor.
2. The product can be directly through the resistance sampling, easy to use (FigureII).











Audited Supplier