HPM series is a modular uninterruptible power supply (UPS) for medium - and large-sized data centers. It features high efficiency (96%) and a high input factor of 0.99, minimizing UPS energy consumption. The modular design and the N+X parallel redundancy technology, making the expansion & management easier as well as reduce initial acquisition costs.
It supports hot-swappable and reduces the maintenance time to 5 minutes and improves system availability. The maximum capacity can be expanded to 1000kva according to future needs, helping to lower initial investment.
General Features
| Adopting digital control design, and the control system is more reliable |
| High input factor 0.99 and output factor 1. |
| 3-level topology design, efficiency is up to 96% |
| Support parallel expansion for cabinet, and parallel expansion is up to 4-6 cabinets. |
| Batteries number of each group can be selected from 30 pieces to 50 pieces. |
| With 7 inches (standard) and 10 inches (optional) colorful touch LCD screen |
Technical Specification
| Module Model | HPM3300E-RM-40 | HPM3300E-RM-50 | |
| Cabinet Model | HPM3300E-200/320/400 | HPM3300E-200/300/400/500/600/800/1000 | |
| Cabinet capacity (VA) | 200k~400k | 200k~1000k | |
| Module capacity (VA) | 40k | 50k | |
| Max. Number | 05/8/10 | 4/6/8/10/12/16/20 | |
| INPUT | |||
| Nominal voltage | 380/400/415Vac, (3Ph+N+PE) | ||
| Operating voltage range | 138~305Vacfor 40% Load; 305~485Vac for 100% Load; | ||
| Operating frequency range | 40Hz-70Hz | ||
| Power factor | ≥0.99 | ||
| Harmonic distortion (THDi) | ≤3% (100% linear load) | ||
| Bypass voltage range | Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) | ||
| Min. voltage: -45% (optional-10%, -15%, -20%, -30%) | |||
| Bypass Frequency range | Frequency protection range: ±10% | ||
| Power Walk In | Support | ||
| Generator input | Support | ||
| OUTPUT | |||
| Rated voltage | 380/400/415Vac, (3Ph+N+PE) | ||
| Power factor | 1 | ||
| Voltage regulation | ±1% | ||
| Output frequency | Line Mode | Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) | |
| Bat. Mode | (50/60±0.1%)Hz | ||
| Crest factor | 0.125694444 | ||
| Harmonic distortion (THDv) | ≤1% with linear load; ≤3% with nonlinear load | ||
| Efficiency | up to 96% | ||
| BATTERY | |||
| Battery voltage | Optional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs optional); | ||
| 360Vdc~600Vdc (30~50 pcs, 36 pcs default, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8) | |||
| Power module charge current | 20A (Max.) | ||
| SYSTEM FEATURES | |||
| Transfer time | Utility to Battery : 0ms; Utility to bypass: 0ms | ||
| Overload | Line Mode | ≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. | |
| Bypass Mode | 135% overload for long term; >1000% overload for 100 ms | ||
| Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately | ||
| Low battery voltage | Alarm and Switch off | ||
| Self-diagnostics | Upon Power On and Software Control | ||
| Backfeed | Support | ||
| EPO | Shut down UPS immediately (turn to bypass optional) | ||
| Battery | Advanced Battery Management | ||
| Noise suppression | Complies with EN62040-3 | ||
| Audible & Visual alarms | Line Failure, Battery Low, Overload, System Fault | ||
| Status LED & LCD display | Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault | ||
| Reading on the LCD display | Input, Output, Battery, Command, Setting, Maintenance | ||
| Communication interface | RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional) | ||
| ENVIRONMENTAL | |||
| Operating temperature | 0ºC~40ºC | ||
| Storage temperature | -25ºC~55ºC | ||
| Humidity range | 0~95% (non condensing) | ||
| Altitude | <1500m, derating required when >1500m | ||
| Noise level(from 1M distance) | <68dB | <73dB | |
| PHYSICAL | |||
| Dimension WxD×H (mm) | UPS cabinet | 200/320kVA: 600×850×2000 | 200/300/400kVA: 600×850×2000 |
| (S / F) | 400kVA: 1200×850×2000 | ||
| Power module | 440×620×130 | ||
| Net weight (kg) | UPS cabinet | 210~460 | 200kVA: 240; 300kVA: 260; 400kVA: 290; |
| (S / F) | 500kVA: 480; 600kVA: 540; 800kVA: 960; | ||
| 1000kVA: 1050 | |||
| Power module | 33 | 34 | |
| STANDARDS | |||
| Safety | IEC/EN62040-1, IEC/EN62477-1 | ||
| EMC | IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8) | ||