| JDEC 700kw biogas generator set data | |
| Genset model | 700GF-N |
| Engine model | H16V190ZLDZ |
| Alternator model | IFC6 Series or equivalent |
| Control panel | GPL 1000 |
| Rated voltage | 10.5kV |
| Power factor | 0.8 (lagging) |
| Rated frequency | 50/60Hz |
| Rated speed | 1000/1200rpm |
| Starting method | 24V DC start |
| Voltage regulating method | AVR (Automatic voltage regulation) |
| Speed governing method | Electronic governor |
| Ignition system | Digital ignition system |
| Cooling mehtod | Forced water cooling with multi-fans radiator |
| Coupling method | Flexible coupling |
| Reference dimension | 9205x2350x2610mm (the drawing will be presented after signing of contract) |
| Reference weight | 24500kg |
| Biogas engine data | |
| Model | H16V190ZLDZ |
| Engine type | Four strokes, spark plug ignited, turbocharged and water cooled |
| Cylinder arrangement | V type, 60° |
| Bore | 190mm |
| Stroke | 210mm |
| Displacement | 95.27L |
| Rated speed | 1000rpm |
| Idle speed | 700rpm |
| Lube oil consumption | ≤0.8g/kwh |
| Exhaust temperature (before turbo) | ≤650ºC |
| Jacket water outlet temperature | ≤85ºC |
| Lube oil temperature in oil pan | ≤90ºC |
| Oil pressure in main oil passage | 400-800kpa |
| Oil pressure in turbocharger | 200-400kpa |
| Steady speed regulation | 0-5% adjustable |
| Cooling method | Forced water cooling, multi-fans radiator |
| Lubricating method | Pressure and splashing lubricating |
| Ignition method | Spark plug ignition |
| Starting method | 24V DC start |
| Rotating direction | Counterclockwise (flywheel view) |
| Output method | Flywheel output |
| Alternator data | |
| Model | IFC6 series or equivalent |
| Rated capacity | 1250kva |
| Rated voltage | 10.5kV |
| Rated frequency | 50Hz |
| Power factor | 0.8 (lagging) |
| Rated speed | 1000rpm |
| Protection class | IP23 |
| Insulation class | H |
| Phases and connection | 3 phases and 4 wires |
| Exciting method | Brushless |
| Voltage regulating method | AVR automation |
| Steady state voltage regulation ratio | ≤±2.5% |
| Transient voltage regulation ratio | ≤+20% (-15%) |
| Voltage settling time | ≤ 1.5s |
| Voltage fluctuation ratio | ≤1% |
| Steady state frequency regulation ratio | 0-5% |
| Transient frequency regulation ratio | ≤±10% |