Cast resin insulation guarantees secure performance of the transformer with no need for complicatedand costly maintenance. Preventive maintenance of cast resin transformers consists in a simple visualcheck. Low operating costs Low losses in the magnetic core and in the windings reduce the costs ofoperation. The coils are made with pure copper wire /foil, and encapsulated by high quality epoxy resin.

Rated capacity (KVA) | HV | LV | Vector Group | No-load current (%) | No-load loss(W) | Load loss(W) | Impedance (%) | ||
130ºC(B) | 150ºC(F) | 180ºC(H) | |||||||
30 | 6.3 10 11 | 0.4 | dyn11 Yyn0 Dyn5 | 2 | 190 | 670 | 710 | 760 | 4.5 |
50 | 2 | 270 | 940 | 1000 | 1070 | ||||
80 | 1.5 | 370 | 1290 | 1380 | 1480 | ||||
100 | 1.5 | 400 | 1480 | 1570 | 1690 | ||||
125 | 1.3 | 470 | 1740 | 1850 | 1980 | ||||
160 | 1.3 | 540 | 2000 | 2130 | 2280 | ||||
200 | 1.1 | 620 | 2370 | 2530 | 2710 | ||||
250 | 1.1 | 720 | 2590 | 2760 | 2960 | ||||
315 | 1.0 | 880 | 3270 | 3470 | 3730 | ||||
400 | 1.0 | 980 | 3750 | 3990 | 4280 | ||||
500 | 1.0 | 1160 | 4590 | 4880 | 5230 | ||||
630 | 0.85 | 1340 | 5530 | 5880 | 6290 | 6.0 | |||
800 | 0.85 | 1520 | 6550 | 6960 | 7460 | ||||
1000 | 0.85 | 1770 | 7650 | 8130 | 8760 | ||||
1250 | 0.85 | 2090 | 9100 | 9690 | 10300 | ||||
1600 | 0.85 | 2450 | 11000 | 11700 | 12500 | 8.0 | |||
2000 | 0.7 | 3050 | 13600 | 14400 | 15500 | ||||
2500 | 0.7 | 3600 | 16100 | 17100 | 18400 |